Permit Number: TC-COM-0823-02094
Parcel: 125101380

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0823-02094
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2026 Commercial Electrical Standard APPROVED Electrical (E) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 2/9/2026
The electrical review is approved. Subject to the field inspector’s approval.
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
02/09/2026 Commercial Building Standard REQUIRES RESUBMIT uilding (B) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Denied
Date Completed: 2/9/2026
1.Unresolved - Sheets G-000, G-003 / Floor Plan / Incorrectly calculated occupant load.The concentrated occupant
area (standing) at 1 occupant per 5sf is to be calculated using the floor space up to the ordering counter. The break
room with tables and chairs is to be calculated at 1 occupant per 15sf. Correct and coordinate the occupant load
calculations, plumbing fixture count, and egress calculations on sheet G-003 with the load specified on sheet G-000.
(2018 IBC section 1004)
i.Classification (2-9-26): The occupant load listed on sheet G-000 under Building Data does not match the
calculated occupant load.
2.Resolved - Sheet A-604 / Architectural interior elevations / The revised interior elevations were not provided in the
revised set.Provide the full set of sheets affected by the revisions. (2018 IBC section 107)
02/05/2026 PDSD Application Completeness Express REVIEW COMPLETED REVIEW 2; SEE REVISE PERMIT WORKFLOW DATED 12/18/2025. THIS REVIEW STARTED DUE TO WORKFLOW ISSUE.