Permit Number: TC-COM-0823-02094
Parcel: 125101380

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-02094
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/07/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/6/2023 11:07:55 AM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/6/2023 11:06:16 AM
1) Resolved - General: Detail what equipment is in the play area room. (2018 IBC section 107)

2) Resolved - General: Include the details showing the envelope energy compliance for the walls, ceiling, windows, and doors. (2018 IECC section C402)

3) Resolved - General: Provide the gas piping floor plan layout, diagram, and calculations. Include the loads and specifications of all gas fired appliances. (2018 IBC section 107)

4) Resolved - General: Guards are required for roof hatches within 10 ft of the roof edge. Show the guards as required by 2018 IBC section 1011.13.

5) Unresolved - Sheet A-701 (Toilet Rooms): Include the minimum required accessible toilet compartment space dimensions for both the men's and women's rooms. (2009 ICC A117.1 section 604.9.2) The revised clear spaces do not meet the
required 59" deep x 60" wide clear floor spaces for floor mounted toilet room compartments.

6) Unresolved - Sheet A-701 (Toilet Rooms): The men's accessible toilet compartment shows the door swinging into the required space. (2009 ICC A117.1 section 604.9.3) The clear floor spaces were reduced in size and if show the correct
dimensions, the door will swing into the required 60"x59" clear floor space.

7) Unresolved - Sheet A-701 (Toilet Rooms): Coordinate the women's toilet room door swing direction with all sheets. many sheets show reversed swing. Doors with closers need a minimum of 12 inches of maneuvering clearance on the latch side of
the door (not provided on the push side of the women's room). (2009 ICC A117.1 section 404.2.3.5) The women's toilet room door does not have the required 12" space on the latch side from the push side of the door.

8) Unresolved - Sheets A-701 (Toilet Rooms), F-201 (Signage Details): Show the location of the accessible sign on the latch side of the women's toilet room door. (2009 ICC A117.1 section 703.3.11) Sheet A-701 shows signage locations on both the latch and hinge sides of the women's toilet room door. Sheet F-201 shows the toilet room sign only on the hinge side of the door. Please correct and coordinate the signage location and details.

9) Resolved - Sheets A-908 and P-101 (Details): Some details are not legible. (2018 IBC section 107)

10) Unresolved - Sheet P-101 (Plumbing Drawings): Provide the DWV isometric diagram and drainage fixture unit calculations for pipe sizing. (2018 IPC section 106.3.1, 2018 IBC section 107) The sheet P-301 referenced in the response to review comments letter was not included in the revised plans.

11) Resolved - Sheet P-101 (Plumbing Drawings): Provide grease interceptor location and details in the drawings and diagrams. (2018 IPC section 106.3.1, 2018 IBC section 107)

12) Resolved -Sheet P-201 (Plumbing Drawings): Provide the water supply isometric diagram and calculations for pipe sizing. (2018 IPC section 106.3.1, 2018 IBC section 107)

13) Resolved - Sheet E-201 (Electrical Drawings): The play area light and emergency light details are not shown. (2018 IBC section 1008.3)

14) Unresolved - Sheet E-202 (Electrical Drawings): Only parts of the electrical power plans are shown. Please provide the full floor power plans including the panel locations. (2018 IBC section 107) The dining, playroom, toilet rooms, lobby, entrances, etc. are still not included in the electrical power plans.

15) Resolved - Sheet M-201 (Mechanical Drawings): Provide the mechanical equipment schedule. (2018 IBC section 107)



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/6/2023 11:07:22 AM
See the building review comments.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/6/2023 11:07:07 AM
See the building review comments.




Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/6/2023 11:07:39 AM
See the building review comments.
11/14/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL Nicholas Martell, Principal Planner TC-COM-0823-02094 Commercial Addition November 14, 2023 The commercial plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed. 1. While the plans appear to match TD-DEV-0123-00102, Zoning cannot approve until the Development Package is approved. To resubmit your plans for additional review, please visit: https://tdc-online.tucsonaz.gov/energov_prod/selfservice#/home If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov Don't hesitate to reach out once the DP is approved and the building plans are resubmitted to avoid a longer review delay.
11/03/2023 PDSD Application Completeness REVIEW COMPLETED