Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/07/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/7/2024 8:12:45 AM
NO REVISIONS WERE MADE

1. Resolved - General: Detail what equipment is in the play area room. (2018 IBC section 107)
2. Resolved - General: Include the details showing the envelope energy compliance for the walls, ceiling, windows, and doors. (2018 IECC section C402)
3. Resolved - General: Provide the gas piping floor plan layout, diagram, and calculations. Include the loads and specifications of all gas fired appliances. (2018 IBC section 107)
4. Resolved - General: Guards are required for roof hatches within 10 ft of the roof edge. Show the guards as required by 2018 IBC section 1011.13.
5. Unresolved - Sheet A-701 (Toilet Rooms): Include the minimum required accessible toilet compartment space dimensions for both the men's and women's rooms. (2009 ICC A117.1 section 604.9.2) The revised clear spaces do not meet the required 59" deep x 60" wide clear floor spaces for floor mounted toilet room compartments.
6. Unresolved - Sheet A-701 (Toilet Rooms): The men's accessible toilet compartment shows the door swinging into the required space. (2009 ICC A117.1 section 604.9.3) The clear floor spaces were reduced in size and don’t show the required dimensions for an accessible toilet compartment, the door will swing into the required 60"x59" clear floor space.
7. Unresolved - Sheet A-701 (Toilet Rooms): Coordinate the women's toilet room door swing direction with all sheets. Many sheets show reversed swing. Doors with closers need a minimum of 12 inches of maneuvering clearance on the
latch side of the door (not provided on the push side of the women's room). (2009 ICC A117.1 section 404.2.3.5) The women's toilet room door does not have the required 12" space on the latch side from the push side of the door. Show
the required maneuvering clear floor space.
8. Unresolved - Sheets A-701 (Toilet Rooms), F-201 (Signage Details): Show the location of the accessible sign on the latch side of the women's toilet room door. (2009 ICC A117.1 section 703.3.11) Sheet A-701 shows signage locations
on both the latch and hinge sides of the women's toilet room door. Sheets F-201 through F-701 show the toilet room sign only on the hinge side of the door. Please correct and coordinate the signage location and details on all relevant
sheets.





Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/7/2024 8:13:40 AM
NO REVISIONS WERE MADE
1. Resolved - Sheet E-201 (Electrical Drawings): The play area light and emergency light details are not shown. (2018 IBC section 1008.3)
2. Unresolved - Sheet E-202 (Electrical Drawings): Only parts of the electrical power plans are shown. Please provide the full floor power plans including the panel locations. (2018 IBC section 107) The dining, playroom, toilet rooms, lobby, entrances, etc. are still not included in the electrical power plans.
3. Resolved - Sheet M-201 (Mechanical Drawings): Provide the mechanical equipment schedule. (2018 IBC section 107)




Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/7/2024 8:14:36 AM
NO REVISIONS WERE MADE
1. Unresolved - Sheet A-701 (Toilet Rooms): Include the minimum required accessible toilet compartment space dimensions for both the men's and women's rooms. (2009 ICC A117.1 section 604.9.2) The revised clear spaces do not meet the required 59" deep x 60" wide clear floor spaces for floor mounted toilet room compartments.
2. Unresolved - Sheet A-701 (Toilet Rooms): The men's accessible toilet compartment shows the door swinging into the required space. (2009 ICC A117.1 section 604.9.3) The clear floor spaces were reduced in size and don’t show the required dimensions for an accessible toilet compartment, the door will swing into the required 60"x59" clear floor space.
3. Unresolved - Sheet A-701 (Toilet Rooms): Coordinate the women's toilet room door swing direction with all sheets. Many sheets show reversed swing. Doors with closers need a minimum of 12 inches of maneuvering clearance on the
latch side of the door (not provided on the push side of the women's room). (2009 ICC A117.1 section 404.2.3.5) The women's toilet room door does not have the required 12" space on the latch side from the push side of the door. Show the required maneuvering clear floor space.
4. Unresolved - Sheets A-701 (Toilet Rooms), F-201 (Signage Details): Show the location of the accessible sign on the latch side of the women's toilet room door. (2009 ICC A117.1 section 703.3.11) Sheet A-701 detail A2 shows signage
locations on both the latch and hinge sides of the women's toilet room door. Sheets F-201 through F-701 show the toilet room sign only on the hinge side of the door. Please correct and coordinate the signage location and details on all relevant sheets.
5. Resolved - Sheets A-908 and P-101 (Details): Some details are not legible. (2018 IBC section 107)
6. Unresolved - Sheet P-101 (Plumbing Drawings): Provide the DWV isometric diagram and drainage fixture unit calculations for pipe sizing. (2018 IPC section 106.3.1, 2018 IBC section 107) The sheet P-301 referenced in the
response to review comments letter was not included in the revised plans.
7. Resolved - Sheet P-101 (Plumbing Drawings): Provide grease interceptor location and details in the drawings and diagrams. (2018 IPC section 106.3.1, 2018 IBC section 107)
8. Resolved -Sheet P-201 (Plumbing Drawings): Provide the water supply isometric diagram and calculations for pipe sizing. (2018 IPC section 106.3.1, 2018 IBC section 107)
09/03/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0823-02094 – TD-DEV-0123-00102
3605 E BROADWAY BL. – C-1/C-2
Food Service (4th Review)

TRANSMITTAL: September 3, 2024

Resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1/C-2 Zone (UDC 4.7.20/.21). Food Service is an allowed use in the zone (Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5-7 and 4.9.13.O/ 4.9.4.M.1, .6, & .7 and 4.9.13.P.

1. While the plans appear to match TD-DEV-0123-00102, Zoning cannot approve until the Development Package is approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/06/2024 PDSD Application Completeness REVIEW COMPLETED