Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.2

Permit Number - TC-COM-0823-02094
Review Name: COMMERCIAL REVIEW - FULL REVISION v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/01/2026 Commercial Building Standard REQUIRES RESUBMIT Building (B) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Denied
Date Completed: 4/1/2026
1.Unresolved - Sheets G-000, G-003 / Floor Plan / Incorrectly calculated occupant load.The concentrated occupant
area (standing) at 1 occupant per 5sf is to be calculated using the floor space up to the ordering counter. The break
room with tables and chairs is to be calculated at 1 occupant per 15sf. Correct and coordinate the occupant load
calculations, plumbing fixture count, and egress calculations on sheet G-003 with the load specified on sheet G-000.
(2018 IBC section 1004)
i.Classification (4-1-26): The occupant loads listed on sheet G-000 under Building Data and egress calculations
(sheet G-003) do not match the calculated occupant load. The response narrative states amendments to the
plans but were not included in the plans that were submitted.