Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0823-02055
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2024 | Site Engineering | APPROVED | |||
| 08/14/2024 | Site Zoning | APPROVED | |||
| 08/19/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/18/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Building(B) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 7/18/2024 8:09:39 AM 1. Sheets PT-1 and PT-2 do not have the engineer’s seal. (2018 IBC section 106) 2. Sheet 11B: Detail 6 identifies the installation of a drinking fountain. Include the accessibility details, plumbing and electrical plans for the drinking fountain(s). The drinking fountain location is not shown on the original site plans. (2018 IBC section 106, 2009 ICC A117.1 section 602) |
||
| 07/17/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |