08/19/2024 Site Engineering APPROVED
08/14/2024 Site Zoning APPROVED
08/19/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/18/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 7/18/2024 8:09:39 AM
1. Sheets PT-1 and PT-2 do not have the engineer’s seal. (2018 IBC section 106)
2. Sheet 11B: Detail 6 identifies the installation of a drinking fountain. Include the accessibility details, plumbing and electrical plans for the drinking fountain(s). The drinking fountain location is not shown on the original site plans. (2018
IBC section 106, 2009 ICC A117.1 section 602)