Permit Number: TC-COM-0823-02054
Parcel: 136130040

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.5

Permit Number - TC-COM-0823-02054
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2024 Site Engineering APPROVED
02/08/2024 Bldg Permits - Post Review Express REVIEW COMPLETED
02/07/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 11/30/2023 6:52:35 PM


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 2/7/2024 1:34:56 AM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 9/20/2023 9:07:22 AM




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 9/19/2023 9:17:55 AM
Electrical Review of Super Star Car Wash
By: Ron Ross PE

E1.0 SITE PLAN: Missing Keynote 10.

E1.1 SITE LIGHTING & POWER PLAN: Missing Keynote, 5 & 6 used in details 1&2.

E2.0 LIGHTING & POWER PLAN:

Missing Keynote 5 or mis-identified and should be Keynote 3.

Could not locate Power Keynotes 4 & 5.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 2/5/2024 10:04:54 PM
Third plumbing review: OK Subject to Field Inspections

Resolved-1). plan set missing site utility piping plan pages C4.1, C4.2, C4.3 -IPC 106.3.1

Resolved-2). Plan set missing 11 of the 14 plumbing pages shown on plan page T1.0 -IPC 106.3.1

Resolved-3). Oil interceptor on plan pages P1.0 & P1.1 needs to be vented -IPC 1003.9

Resolved-4). Commercial Washing machine needs lint interceptor on plan page P1.1 -IPC 1003.6

5). Resolved-The 2.5 " carwash connection on plan page P1.2 needs its own RPZ backflow -IPC 608.1** there needs to be an additional RPZ Backflow on the car wash line separate from the RPZ on main water @ bldg entrance **

Resolved-6). Water line to mat wash needs RPZ backflow on plan page P1.2 - IPC 608.1

Resolved-7), Washing machine on plan pages P1.2 & P1.3 needs to be piped with hot water. -IPC 607.1

8). Resolved- Roof drain riser diagram on plan page P1.1 only shows 2 sets of roof drains, Roof plan on same page shows 3 sets. Diagrams need to correlate -IPC 106.3.1

Resolved-9). Roof drain riser diagram on plan page P1.1 needs to show the total GPM load at each set of roof drains, and each point of interconnection & termination. -IPC 1106.2

Resolved-10). Can't do complete plumbing review until all plan pages are present -IPC 106.3.
02/01/2024 PDSD Application Completeness Express REVIEW COMPLETED