Permit Number: TC-COM-0823-02054
Parcel: 136130040

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-02054
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/21/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Denied
Reason:
Date Completed : 9/14/2023 2:07:06 PM
1. Structural steel, components and fasteners that are exposed are to be protected against corrosion in accordance with AISC 360 Section B.13 as indicated in IBC 2018 Section 2203.1.
2. Designer is to coordinate venting and drainage hole requirements for HSS tube members that are galvanized using the hot-dip galvanizing process. Provide for plugs as needed.
◦ AWS D-19.0 calls for welds on galvanized steel to be free of zinc. Field welds on galvanized parts requires the removal of the zinc coating in the area of weld. Provide zinc paint (approved by the galvanizer) and apply as required to the weld and steel area to provide protection.
3. Provide galvanized bolts on the framing connections that are galvanized.
4. DEFERRED SUBMITTAL REQUIREMENTS
Structural general notes are to include any components of the building that may be considered deferred submittals. IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official.
If items will be deferred the plans are to clearly note the following per IBC Section 107.3.4.1:
* To be reviewed by design professional in responsible charge.
* Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.
* They shall be submitted for review by the building official.
* Shall not be installed until approved by building official.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.




Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 9/21/2023 4:18:38 AM
1. Sheet T1.0. Add 2018 International Fire Code, the City of Tucson/ Pima County Outdoor Lighting Code and the ICCA117.1- 2009 Accessible and Usable Buildings and Facilities to the list of applicable codes. (General Comment).
2. Sheet T1.0. Update the sheet index to match the drawing titles in the set. The Mechanical, Plumbing and Electrical sheets do not coordinate with the index. (General Comment).
3. Sheet T2.0. Correct the General Construction Notes, the notes have been cut off at the bottom of the page and are not readable. (General Comment).
4. Sheet LS1.0. Correct the North arrow on the plans to coordinate with the site plan. (General Comment)
5. Sheet A1.0. Clarify what Keynote 3273 is to indicate, it is not identified. (General Comment).
6. Sheet A2.1. Correct the North arrow on the slab plan to coordinate with the site plan. (General Comment).
7. Sheet A2.1. and sheet A2.2. Provide dimensions for the Mat Wash area on the plans. (General Comment).
8. Sheet A2.1. Correct the Assemblies Legend that indicates to see sheet A0.1. There is no sheet A0.1 included in the set. (General Comment). Coordinate all plans.
9. Sheet A2.3. Correct General Note 2 that indicates to see assembly sheet A0.1 for complete wall, floor, and roof assembly information. There is no sheet A0.1 included in the set. (General Comment). Coordinate all plans.
10. Sheet A4.0. Indicate the thermal insulation barrier for both the office and the restroom that are provided with mechanical heat/ cooling. The enlarged floor plans indicate that wall a1.0a has no insulation and that wall a2.0a calls out for sound batting only. Clarify the insulation locations and values on the plans that are in accordance with the 2018 IECC. Correct the building sections to show the location of all insulation for the structure.




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 9/20/2023 9:07:22 AM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/19/2023 9:17:55 AM
Electrical Review of Super Star Car Wash
By: Ron Ross PE
E1.0 SITE PLAN: Missing Keynote 10.
E1.1 SITE LIGHTING & POWER PLAN: Missing Keynote, 5 & 6 used in details 1&2.
E2.0 LIGHTING & POWER PLAN:
Missing Keynote 5 or mis-identified and should be Keynote 3.
Could not locate Power Keynotes 4 & 5.




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 9/20/2023 9:31:51 PM
First plumbing review:
1). plan set missing site utility piping plan pages C4.1, C4.2, C4.3 -IPC 106.3.1
2). Plan set missing 11 of the 14 plumbing pages shown on plan page T1.0 -IPC 106.3.1
3). Oil interceptor on plan pages P1.0 & P1.1 needs to be vented -IPC 1003.9
4). Commercial Washing machine needs lint interceptor on plan page P1.1 -IPC 1003.6
5). The 2.5 " carwash connection on plan page P1.2 needs its own RPZ backflow -IPC 608.1
6). Water line to mat wash needs RPZ backflow on plan page P1.2 - IPC 608.1
7), Washing machine on plan pages P1.2 & P1.3 needs to be piped with hot water. -IPC 607.1
8). Roof drain riser diagram on plan page P1.1 only shows 2 sets of roof drains, Roof plan on same page shows 3 sets. Diagrams need to correlate -IPC 106.3.1
9). Roof drain riser diagram on plan page P1.1 needs to show the total GPM load at each set of roof drains, and each point of interconnection & termination. -IPC 1106.2
10). Can't do complete plumbing review until all plan pages are present -IPC 106.3.1
09/11/2023 Fire New Construction REQUIRES RESUBMIT -Conflicting information concerning fire sprinklers. Sheet T1.0 project scope indicates fire sprinklers will be a deferred submittal. Same sheet, project summary, indicates fire sprinklers will not be installed. Sheet LS1.0 indicates fire sprinklers will not be installed in code summary however the interior wall ceiling finish table you provided indicates sprinklered building.
-Sheet LS1.0 indicates a fire alarm will be installed. Building fire alarm not required in this building. Verify fire alarm will be installed.
john.vincent@tucsonaz.gov
5203495581
09/22/2023 Site Engineering REQUIRES RESUBMIT This permit cannot be approved until its associated development package, TD-DEV-0623-00289, has been approved.

Lianne Evans
lianne.evans@tucsonaz.gov
09/29/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0823-02054 – TD-DEV-0623-00289
8690 E. Golf Links Rd. – Existing C-1 - Proposed C-2
Self-Service Drive Thru Car wash (1st Review)

TRANSMITTAL: September 29, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 Zone (UDC 4.7.21). Automotive: Minor Service and Repair – Self Serve Car Wash is an allowed use in the zone, subject to Use Specific Standard 4.9.13.E.

1. Zoning has reviewed the building plans for compliance with Development Package TD-DEV-0623-00289, and the Site plan provided does not match the DP. The southern most vacuum area and trash enclosure do not match. Unit the site and DP plans match and the DP is approved by all review agencies Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/04/2023 Water - PDSD REQUIRES RESUBMIT Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
09/06/2023 PDSD Application Completeness Express REVIEW COMPLETED