Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0823-02049
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/02/2024 | Commercial Mechanical | APPROVED | |||
01/02/2024 | Commercial Structural | APPROVED | |||
01/02/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
01/02/2024 | Commercial Plumbing | REQUIRES RESUBMIT | If the 3-compartment sink is used only for washing, rinsing, and sanitizing utensils used for food service, the sink shall drain indirectly to the grease interceptor with an air gap or an air break. If, however, the 3-compartment sink is also used for the preparation of food items, separate indirect waste pipes shall be provided for each compartment to protect against cross-contamination or fouling and each indirect drain shall terminate with an air gap. Reference: Sections 801.2, 802.1.1, and 802.1.7, IPC 2018. [Initial comment: Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer. If a grease interceptor is not in place, show how the public sewer is to be protected from harmful discharges. Reference: Section 1003.1, IPC 2018.] | ||
12/05/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |