Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-02037
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2023 Commercial Structural APPROVED
08/29/2023 Site Zoning APPROVED
10/04/2023 Water - PDSD APPROVED
08/23/2023 Site Engineering NOT REQUIRED
10/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/25/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and prvide a written response.

1. It appears that the whole laundry room is being re wired and fitted with new electrical devices and lighting. This is determined because of the bold print for most devices, lighting and wiring. The scope of work submitted with the application and plans simply states, "Tenant Improvement to expand laundry”.

2.Also provide complete compliance with the 2018 IECC, 2012 City of Tucson Outdoor Lighting Code, 2017 NEC, 2018 IBC section 1008 (Means of Egress Illumination) where applicable..

3. Why does the panel schedule make references to ‘Dwelling Unit’ in the branch circuits descriptions? Is this a ‘Dwelling Unit’ or a ‘Laundry facility’?

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal requirements.
09/20/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Show the size, route, and termination of the new dryer exhaust ducts. Reference: Sections 504.1, 504.2, and 504.4, IMC 2018.
2. Show how make up air is being provided for the dryers. Reference: Section 504.6, IMC 2018.
09/20/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Central laundry rooms containing automatic clothes washers in multi-family dwellings shall have a floor drain to drain the entire floor area. The minimum drain outlet is 3”. Reference: Section 413.4, IPC 2018.
2. Provide a lint separator for the automatic clothes washers. Reference: Section 1003.6, IPC 2018.
09/06/2023 Fire New Construction REVIEW COMPLETED
08/22/2023 PDSD Application Completeness Express REVIEW COMPLETED