Permit Number: TC-COM-0823-02034
Parcel: 12801011C

Address:
324 S WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-02034
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2024 Site Engineering APPROVED
10/21/2024 Site Zoning APPROVED
10/30/2024 Water - PDSD APPROVED Rejected by Zoning at Re-stamp
10/30/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT Rejected by Zoning at Re-stamp
10/14/2024 External Reviewers - Stantec REQUIRES RESUBMIT October 14, 2024
3rd Review

Centennial American Properties
Attn: Jason Tankersley
1200 East Morehead, Suite 280
Charlotte, North Carolina 28204

Re: CAP STORAGE - WILMOT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0823-02034
Stantec Project Number: 185215066
Stantec File Number: TUC-24-095

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 102,880 222 Yes No
Separate Permits: Automatic fire sprinklers and signage.
Deferred Submittals: Metal stairs, storefront and window system, elevator shop drawings, prefabricated canopy
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and masonry.

ARCHITECTURAL COMMENTS

Sheet A001

1. Addressed.

2. Addressed.

3. Addressed.

Sheet A002

1. Addressed.

Sheet A010

1. Addressed.

Sheet A100

1. Addressed.

2. Addressed.

Sheet A102.1

1. Addressed.

Sheet A131

1. Addressed.

Sheet A500

1. Addressed.

Sheet A920

1. Addressed.

STRUCTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. New Comment: The structural sheets are not signed and sealed by the engineer of record. Please re-submit with these sheets sealed and signed. [Ref. IBC 2018 107.1]

Sheet S120

1. Addressed.

Sheet S501

1. Addressed.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P101

1. Addressed.

ELECTRICAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com


October 14, 2024
3rd Review

Centennial American Properties
Attn: Jason Tankersley
1200 East Morehead, Suite 280
Charlotte, North Carolina 28204

Re: CAP STORAGE - WILMOT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0823-02034
Stantec Project Number: 185215066
Stantec File Number: TUC-24-095

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 102,880 222 Yes No
Separate Permits: Automatic fire sprinklers and signage.
Deferred Submittals: Metal stairs, storefront and window system, elevator shop drawings, prefabricated canopy
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and masonry.

ARCHITECTURAL COMMENTS

Sheet A001

1. Addressed.

2. Addressed.

3. Addressed.

Sheet A002

1. Addressed.

Sheet A010

1. Addressed.

Sheet A100

1. Addressed.

2. Addressed.

Sheet A102.1

1. Addressed.

Sheet A131

1. Addressed.

Sheet A500

1. Addressed.

Sheet A920

1. Addressed.

STRUCTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. New Comment: The structural sheets are not signed and sealed by the engineer of record. Please re-submit with these sheets sealed and signed. [Ref. IBC 2018 107.1]

Sheet S120

1. Addressed.

Sheet S501

1. Addressed.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P101

1. Addressed.

ELECTRICAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com


October 14, 2024
3rd Review

Centennial American Properties
Attn: Jason Tankersley
1200 East Morehead, Suite 280
Charlotte, North Carolina 28204

Re: CAP STORAGE - WILMOT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0823-02034
Stantec Project Number: 185215066
Stantec File Number: TUC-24-095

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 102,880 222 Yes No
Separate Permits: Automatic fire sprinklers and signage.
Deferred Submittals: Metal stairs, storefront and window system, elevator shop drawings, prefabricated canopy
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and masonry.

ARCHITECTURAL COMMENTS

Sheet A001

1. Addressed.

2. Addressed.

3. Addressed.

Sheet A002

1. Addressed.

Sheet A010

1. Addressed.

Sheet A100

1. Addressed.

2. Addressed.

Sheet A102.1

1. Addressed.

Sheet A131

1. Addressed.

Sheet A500

1. Addressed.

Sheet A920

1. Addressed.

STRUCTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. New Comment: The structural sheets are not signed and sealed by the engineer of record. Please re-submit with these sheets sealed and signed. [Ref. IBC 2018 107.1]

Sheet S120

1. Addressed.

Sheet S501

1. Addressed.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P101

1. Addressed.

ELECTRICAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
10/22/2024 Fire New Construction REQUIRES RESUBMIT The original life safety notes were deleted from this submittal. Please explain. Here are the notes from the previous submittal that were located on sheet G0.1

"FIRE SPRINKLER UNDERGROUND PLANS SHALL BE SUBMITTED TO AND A PERMIT
OBTAINED FROM TFD.
FIRE SPRINKLER PLANS SHALL BE SUBMITTED TO AND A PERMIT OBTAINED
FROM TFD.
FIRE ALARM PLANS SHALL BE SUBMITTED TO AND A PERMIT OBTAINED FROM TFD.
BUILDING SHALL BE TESTED FOR ERRC BY PCWIN AND THE REPORT PROVIDED TO
TFD PRIOR TO THE TCO.
ELEVATOR SHALL BE COMPLIANT WITH THE 2018 IBC, CHAPTER 30, SECTION 3001.2.
OWNER SHALL PROVIDE KNOX ELEVATOR KEY BOX, KNOX KEY BOXES AND KNOX
LOCKING F.D.C. CAPS.
OWNER SHALL PROVIDE ELEVATOR TWO-WAY COMMUNICATION.
DP SHALL BE APPROVED PRIOR TO BUILDING PERMIT BEING COMPLETED."

john.vincent@tucsonaz.gov
5203495581
10/08/2024 PDSD Application Completeness Express REVIEW COMPLETED