Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0823-02034
Parcel: 12801011C

Address:
324 S WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-02034
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/02/2025 Commercial Building REQUIRES RESUBMIT January 2, 2025
1st Review

Centennial American Properties
Attn: Jason Tankersley
1200 East Morehead, Suite 280
Charlotte, North Carolina 28204

Re: CAP STORAGE – WILMOT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0823-02034
Stantec Project Number: 185215066
Stantec File Number: TUC-24-156

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 102,880 222 Yes No
Separate Permits: Automatic fire sprinklers and signage.
Deferred Submittals: Metal stairs, storefront and window system, elevator shop drawings, prefabricated canopy
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. One of the primary changes to this project was to add an elevator equipment room, and the drawings have been revised to show this room. Further the room is shown as being separated from the rest of the facility with a 1-hour fire barrier. Sheet A341 shows enlarged plans, and Detail 4 shows a section cut through the elevator and the elevator machine room, referencing Detail 1 on Sheet A343. Detail 1 doesn’t identify the elevator machinery room, and further it does not identify the 1-hour horizontal assembly formed at the top of the elevator machinery room, 16 feet above the machinery floor. Please indicate that the elevator machinery room walls AND the floor ceiling assembly that separates this room from the rest of the facility are separated with a 1-hour horizontal assembly as required by 2018 IBC Sec. 3005.4, and further provide on the plans the listing information for this horizontal assembly.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
01/02/2025 Commercial Electrical REQUIRES RESUBMIT January 2, 2025
1st Review

Centennial American Properties
Attn: Jason Tankersley
1200 East Morehead, Suite 280
Charlotte, North Carolina 28204

Re: CAP STORAGE – WILMOT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0823-02034
Stantec Project Number: 185215066
Stantec File Number: TUC-24-156

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 102,880 222 Yes No
Separate Permits: Automatic fire sprinklers and signage.
Deferred Submittals: Metal stairs, storefront and window system, elevator shop drawings, prefabricated canopy
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. One of the primary changes to this project was to add an elevator equipment room, and the drawings have been revised to show this room. Further the room is shown as being separated from the rest of the facility with a 1-hour fire barrier. Sheet A341 shows enlarged plans, and Detail 4 shows a section cut through the elevator and the elevator machine room, referencing Detail 1 on Sheet A343. Detail 1 doesn’t identify the elevator machinery room, and further it does not identify the 1-hour horizontal assembly formed at the top of the elevator machinery room, 16 feet above the machinery floor. Please indicate that the elevator machinery room walls AND the floor ceiling assembly that separates this room from the rest of the facility are separated with a 1-hour horizontal assembly as required by 2018 IBC Sec. 3005.4, and further provide on the plans the listing information for this horizontal assembly.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
01/02/2025 Commercial Mechanical REQUIRES RESUBMIT January 2, 2025
1st Review

Centennial American Properties
Attn: Jason Tankersley
1200 East Morehead, Suite 280
Charlotte, North Carolina 28204

Re: CAP STORAGE – WILMOT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0823-02034
Stantec Project Number: 185215066
Stantec File Number: TUC-24-156

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 102,880 222 Yes No
Separate Permits: Automatic fire sprinklers and signage.
Deferred Submittals: Metal stairs, storefront and window system, elevator shop drawings, prefabricated canopy
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. One of the primary changes to this project was to add an elevator equipment room, and the drawings have been revised to show this room. Further the room is shown as being separated from the rest of the facility with a 1-hour fire barrier. Sheet A341 shows enlarged plans, and Detail 4 shows a section cut through the elevator and the elevator machine room, referencing Detail 1 on Sheet A343. Detail 1 doesn’t identify the elevator machinery room, and further it does not identify the 1-hour horizontal assembly formed at the top of the elevator machinery room, 16 feet above the machinery floor. Please indicate that the elevator machinery room walls AND the floor ceiling assembly that separates this room from the rest of the facility are separated with a 1-hour horizontal assembly as required by 2018 IBC Sec. 3005.4, and further provide on the plans the listing information for this horizontal assembly.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
01/02/2025 Commercial Plumbing REQUIRES RESUBMIT January 2, 2025
1st Review

Centennial American Properties
Attn: Jason Tankersley
1200 East Morehead, Suite 280
Charlotte, North Carolina 28204

Re: CAP STORAGE – WILMOT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0823-02034
Stantec Project Number: 185215066
Stantec File Number: TUC-24-156

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 102,880 222 Yes No
Separate Permits: Automatic fire sprinklers and signage.
Deferred Submittals: Metal stairs, storefront and window system, elevator shop drawings, prefabricated canopy
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. One of the primary changes to this project was to add an elevator equipment room, and the drawings have been revised to show this room. Further the room is shown as being separated from the rest of the facility with a 1-hour fire barrier. Sheet A341 shows enlarged plans, and Detail 4 shows a section cut through the elevator and the elevator machine room, referencing Detail 1 on Sheet A343. Detail 1 doesn’t identify the elevator machinery room, and further it does not identify the 1-hour horizontal assembly formed at the top of the elevator machinery room, 16 feet above the machinery floor. Please indicate that the elevator machinery room walls AND the floor ceiling assembly that separates this room from the rest of the facility are separated with a 1-hour horizontal assembly as required by 2018 IBC Sec. 3005.4, and further provide on the plans the listing information for this horizontal assembly.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
12/30/2024 Fire New Construction REQUIRES RESUBMIT The following items from the 2018 International Fire Code with Local Amendments apply to the proposed project:
1. 2018 IFC section 504.1: Exterior doors and openings required by this code or the International Building Code shall be maintained with ready access for emergency access by the fire department. Plans page A- 500 "Store Front Door and hardware schedule, HW-Set, Note: " Local Fire Authority lock set requirements:" Provide access from the outside of exit discharge doors at exterior stairways to the interior of the facility.
3. Door hardware page to reflect changes. Questions: Sal.erivezjr@tucsonaz.gov
12/16/2024 PDSD Application Completeness Express REVIEW COMPLETED