Permit Number: TC-COM-0823-02017
Parcel: 12109362A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0823-02017
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2024 Site Engineering APPROVED
11/14/2024 Site Zoning APPROVED
11/14/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/10/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 10/10/2024 1:42:51 PM
1. E-1 comment only: Should add comment to have the electrical contractor balance load at DP panels. Currently calculated loads are unbalanced by 20-25%.
2. E-5 Need to call out for tamper proof receptacles in all required locations per NEC 406.12.
10/08/2024 PDSD Application Completeness Express REVIEW COMPLETED