Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.1
Permit Number - TC-COM-0823-02017
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2024 | Site Engineering | APPROVED | |||
| 11/14/2024 | Site Zoning | APPROVED | |||
| 11/14/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/10/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 10/10/2024 1:42:51 PM 1. E-1 comment only: Should add comment to have the electrical contractor balance load at DP panels. Currently calculated loads are unbalanced by 20-25%. 2. E-5 Need to call out for tamper proof receptacles in all required locations per NEC 406.12. |
||
| 10/08/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |