Permit Number: TC-COM-0823-02017
Parcel: 12109362A

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0823-02017
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2023 Site Engineering APPROVED
12/04/2023 Site Zoning APPROVED
11/22/2023 Water - PDSD APPROVED
12/18/2023 Bldg Permits - Post Review Express REVIEW COMPLETED
11/27/2023 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 11/22/2023 2:50:06 PM


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/9/2023 5:10:50 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 10/10/2023 11:33:10 AM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 9/2/2023 2:47:13 PM
Electrical Review of WoodSpring Suites
By: Ron Ross PE
E-1: Panels G404 thru G418 are missing destination/source feeds as compared to Panel G419 thru G436. Arrows shown may not be required. Clarify/correct as required.

E-5: Keynotes 6 and 8 not properly shown.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 10/12/2023 11:11:21 PM
Second Plumbing Review:OK
1). Resolved-Need to Address Bldg. plan review comments 3, 4. 7 & 8. -IPC 403.1, 1106.3, 1106.5, 1108

2). Resolved-Add Roof GPM loads that each set of scuppers & downspouts will be responsible for along with sizing calculations to Plan page A1.3 -IPC 1106.1, 1106.3, 1106.5, 1108

3). Resolved-Plan page M- 2 Detail 2 shows independent wall exhaust & intake for gas water heaters, detail 5 on same shows single concentric wall termination? Plan page needs to correlate. -IFGC 106.3

4). Resolved-Plan page M-2 detail single combustion air louver for gas dryers will need to be within 12" of ceiling -IFGC 304.6.2

5). Resolved-Gas meter location on plumbing floor plan page P-4 isn't clear -IFGC 106.3.1

6). Resolved-Add gas sizing table used to plan page P-6, -IFGC 402.3

7). Resolved-show the P12 trench drain on plan pages P-2 & P-5 -IPC 106.3.1

8). Resolved-Plan Page P1 note #1 is stating carrier toilets? the models selected & Plan page P5 riser diagram don't correlate with carrier toilet rough in style. -IPC 106.3.1

9).Resolved- Coffee water line note #20 on Plan page P4 needs to include an ASSE 1022 or 1024 backflow -IPC 608.17.1.2

10). Resolved-The P11 hose bibs on plan page P-4 need individual shut off valves -IPC 606.2
11/21/2023 PDSD Application Completeness Express REVIEW COMPLETED