Permit Number: TC-COM-0823-02013
Parcel: 10818716A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-02013
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2023 Site Zoning APPROVED
09/18/2023 Water - PDSD APPROVED
08/23/2023 Site Engineering NOT REQUIRED
09/18/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/29/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/28/2023 6:54:10 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/28/2023 6:47:36 PM
1. General: Include the newly framed wall, door, and windows in the envelope proof of energy compliance. (2018 IECC section C402)
2. General: Include the elevation views of the altered wall and patio dining area. (2018 IEBC section 106.2)
3. Sheet DP1 (Building Details): The proposed patio is 536 sf but the building, restaurant, and patio areas in the calculations are for 1132 sf. Please clarify or correct the calculations. (2018 IEBC section 106.2)
4. Sheet A4 (Floor Plan): Show the fire rating details of the existing separation walls between the restaurant addition and the adjacent office spaces. (2018 IBC Table 508.4)
5. Sheet A7 (Accessibility Details): Show the toilet center line distance to the wall. (2009 ICC A117.1 section 602.4)
6. Sheet A7 (Accessibility Details): Include the table accessibility details. (2009 ICC A117.1 section 902)
7. Sheet M1 (Mechanical Drawings): Include the new kitchen equipment schedule and specification sheets. (2018 IEBC section 106.2)
8. Sheet P1 (Plumbing Diagram): Show the toilet vent pipe size. The toilet drain is shown being reduced from 3" to 2". (2018 IPC Table 710.1(1) note a)
9. Sheet P4 (Fixture Details): The faucet specifications do not show that automatic faucets are being installed as required be amended 2018 IPC sections 412.11 and 419.6.



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/28/2023 6:49:37 PM
See the building review comments.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/28/2023 6:48:35 PM
Pending the approval of the other trades. No electrical revisions needed at this time.




Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/28/2023 6:53:31 PM
See the building review comments.
08/25/2023 Fire New Construction REVIEW COMPLETED
08/18/2023 PDSD Application Completeness REVIEW COMPLETED