Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0823-02007
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/22/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The scope of work description,” new service and panel (see submittal)” requires more information in relation to the submitted plans as follows; 1 The panel schedule show 2 panel ‘C’s. Please clarify. 2 Are the sub-panels ‘A’, ‘B’, and ‘C’ new? 3 Show the panel locations in the floor plan. (bedroom) (closet) (Bathroom) ? If located in closet or bathroom, re-locate to a code approved location. NEC 240.24(D)(E), 408.17. 4 Provide Combination Arc Fault protection for all branch circuits as required per NEC art 210.12. 5 Provide GFI protection for all 120 volt 15 and 20 amp receptacles as required per NEC art 210.8(A), including the Dishwasher. NEC 210.8(D). Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 08/17/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |