Permit Number: TC-COM-0823-02004
Parcel: 117090480

Address:
16 W 21ST ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0823-02004
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/21/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The scope of work description,” new service and panel (see submittal)” requires more information in relation to the submitted plans as follows;

1 The panel schedule show 2 panel ‘C’s. Please clarify.

2 Are the sub-panels ‘A’, ‘B’, and ‘C’ new?

3 Show the panel locations in the floor plan. (bedroom) (closet) (Bathroom) ? If located in closet or bathroom, re-locate to a code approved location. NEC 240.24(D)(E), 408.17.

4 Provide Combination Arc Fault protection for all branch circuits as required per NEC art 210.12.

5 Provide GFI protection for all 120 volt 15 and 20 amp receptacles as required per NEC art 210.8(A), including the Dishwasher. NEC 210.8(D).

Ref; 2018 IBC section 107.2.1, 2017 NEC.
08/17/2023 PDSD Application Completeness Express REVIEW COMPLETED