11/21/2023 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT 1. The design information reported for FC-1, FC-2, and FC-3 does not match the information shown on the approved drawings. If the information on the drawing is incorrect, indicate on the drawing the correct information for the diffusers (e.g. number of diffusers and to which fan coil they are connected).
2. Verify the amount of outside air being supplied by FC-1.