Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0823-01984
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/24/2023 Commercial Plumbing REQUIRES RESUBMIT There is insufficient information to determine if the existing gas piping is sufficient to accommodate the identified load of 285,000 BTUH. Provide the developed length of each section of pipe and the minimum gas pressure needed for each appliance according to the appliance manufacturer. Reference: Sections 402.1 and 402.3, IFGC 2018.
08/15/2023 PDSD Application Completeness Express REVIEW COMPLETED