Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0823-01984
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/24/2023 | Commercial Plumbing | REQUIRES RESUBMIT | There is insufficient information to determine if the existing gas piping is sufficient to accommodate the identified load of 285,000 BTUH. Provide the developed length of each section of pipe and the minimum gas pressure needed for each appliance according to the appliance manufacturer. Reference: Sections 402.1 and 402.3, IFGC 2018. | ||