Permit Number: TC-COM-0823-01981
Parcel: 132131240

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-01981
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2023 Bldg Permits - Post Review REVIEW COMPLETED
09/21/2023 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/25/2023 12:19:00 AM
No structural work was included as part of this submittal.




Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 9/20/2023 12:39:00 AM



Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 8/25/2023 12:18:25 AM



Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 9/20/2023 12:39:11 AM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/17/2023 10:19:05 PM
Second Plumbing Review: OK Subject to field inspections
1). Resolved-The #458 Dump sink on plan page Q11 is for the #220 coffee & espresso machines. The Floor sink beneath this dump sink on plan page P1.0 will need to connect to the grease system. -Tucson Plumbing Code amendments
2). Resolved-The 3" Floor sinks connected the grease interceptor on plan page P1.0 can not have a DFU load less than 5. - IPC 709.4 ( the 1.5" dfu value can't be used due to the indirect waste lines are not trapped they ae discharging to a 3" trapped floor sink.)
4). Resolved-Gas water heaters on plan page P0.0 need shut off valves & sediment traps. -IFGC 408.4, 409.5
5). Resolved-Beverage equipment water connections on plan page P1.0 need backflow devices that comply with -IPC 608.17.1
6). Resolved-Side wall to fixture center measurement needs to be added to enlarged restroom plan page A42. -IPC 404.2, 405.3.1