Permit Number: TC-COM-0823-01967
Parcel: 10408078C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-01967
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2023 Site Engineering APPROVED
08/24/2023 Site Zoning APPROVED
08/14/2023 Fire New Construction NOT REQUIRED
09/13/2023 Water - PDSD NOT REQUIRED
10/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/18/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/18/2023 1:22:34 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/18/2023 1:21:42 PM
1) Sheet s1.0 (Structural Notes): The notes specify that the plans are based on soil bearing of 2500 at only 1'-6" deep.

Please submit the geotechnical engineer report showing the soil bearing capacity below the footing depth. (2018 IBC section 1603.1.6)

2) Sheet x2.0 (Footing Sections): The pole light foundation does not specify the diameter. The wall footings are shown to be 3ft wide but the details on sheet s2.0 shows they are only 2'-6" wide. Please coordinate the correct footing size based on the actual soil bearing capacity. (2018 IBC section 107)

3) Sheet es101 (Electrical Site Plan): Keyed notes 7, 8, and 9 show new electrical equipment installed on the new CMU wall.

Please show the equipment and the transformer unistrut rack construction and anchoring to the wall. (2018 IBC section 107)


Mechanical N/A


Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/18/2023 1:22:14 PM
See the building review comments.

Plumbing N/A
08/14/2023 PDSD Application Completeness Express REVIEW COMPLETED