Permit Number: TC-COM-0823-01965
Parcel: 13101071H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-01965
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2023 Site Zoning APPROVED
09/14/2023 Water - PDSD APPROVED
08/17/2023 Site Engineering NOT REQUIRED
09/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/05/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/5/2023 5:33:43 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 8/16/2023 6:15:43 PM
1. Sheet A-0.1: An increased occupant load is being requested as permitted by Section 1004.5.1. Provide a narrative as to the reasoning for the increased occupant load and clear description of the space.

2. General: No site plan has been provided. Provide an architectural site plan.

3. General: Provide within the site plans, drawings that clearly indicate the accessible routes within the site and site arrival points that connect the accessible parking to the accessible entrances that are in accordance with Section 206.2.1 and 206.2.2.

4. Provide evidence of compliance that 60% of the public entrances are accessible in accordance with Section 206.4.1.

5. Provide evidence of compliance that at least one restricted entrance is accessible in accordance with Section 206.4.7.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 8/18/2023 5:25:25 PM




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 8/29/2023 4:44:22 PM
Electrical Review of Zeal
By: Ron Ross PE
E601 ELECTRICAL ONE LINE DIAGRAM: The single line does not look correct. Please call out the Existing generator size and ATS. Currently it is drawn as a 1200-amp ATS and 350 KW Generator, but your ?? emergency panel EB-L?? is only 100 amps.




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 8/27/2023 10:57:19 PM
First Plumbing Review: OK
08/17/2023 Fire New Construction REQUIRES RESUBMIT -If egress doors are being controlled by access key pads, indicate which method of compliance will be used.
IFC 1010.1.9.9 or 1010.1.9.10
john.vincent@tucsonaz.gov
5203495581
08/15/2023 PDSD Application Completeness Express REVIEW COMPLETED