Permit Number: TC-COM-0823-01960
Parcel: 10605002A

Address:
3909 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-01960
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
10/11/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer)
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/31/2023 7:34:01 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/9/2023 1:43:19 PM



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Denied
Reason:
Date Completed : 10/8/2023 1:01:36 AM
1. Provide mechanical schedule showing all new mechanical appliances MC2018,106.3.1) Complied

2. Provide ventilation calculations (IMC2018,403.3.1.1.1) Complied

3. Provide return air to each room (IMC2018,603) Complied

4. Provide mechanical exhaust to both bathrooms (IMC2018,403.3.1.1) Complied

5. Show how you are bringing in fresh outside air to heat pump air handler (IMC2018,403.1) Complied

Please see additional corrections below

6. You are required to exhaust 70 CFM of exhaust air to public restrooms you are exhausting 50 please correct (IMC2018,403.3.1.1)

7. Make up air shall be provided at approximately the same as exhaust air in repair bay (IMC2018,501.4)



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 10/9/2023 6:19:54 PM
2nd Electrical Review of Sunbelt Rentals
By: Ron Ross PE
Need to provide service receptacle for new HVAC system (Mech units 1 &2) . Need to call out for weather proof GFCI service receptacles to be installed next to units to comply with NEC 210.63 requirement.

Need to provide an interior lighting Comcheck to show IECC 2018 compliance. Using new fixtures should pass, but calculations are required by Tucson to prove compliance. May need to provide lighting controls on a timer/motion detector to
meet the current energy codes for lighting. Will need to provide occupancy/vacancy sensor light switch controls for offices.

Comment only: All new panels have the more costly 22 KAIC rating, but your calculations show less than 4,600 amps maximum fault currents for any of the new panels. Why not use standard (and more common and stocked) 10 KAIC rated
panels?



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/10/2023 10:19:12 PM
Second Plumbing Review:
1). Resolved-Need to address building plan review comments 1 & 2 -IPC 106.3.1, 403.1

2). Unresolved -Plumbing Scope not clear -IPC 106.3.1 No response

3). Unresolved -Add water heater(s) manufacture name and model numbers to plan page P1 -IPC 303, 501.5 No response

4). Unresolved - on plan page P1 need asse 1070 mixing valves -IPC 419.5 No response
10/05/2023 PDSD Application Completeness REVIEW COMPLETED