Permit Number: TC-COM-0823-01959
Parcel: 10408075B

Address:
4495 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-01959
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2023 Site Zoning APPROVED
08/17/2023 Site Engineering NOT REQUIRED
08/17/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/17/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/15/2023 5:02:34 PM
Pending the building review comments. No structural revisions needed at this time.


Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/15/2023 4:55:43 PM
1) Sheet CV.0 (Cover sheet): Incorrect energy code shown. The plans are to be designed based on the 2018 IECC.

2) Sheet E1.0 (Electrical Drawings): Include the location and details of the electrical panel supplying power to the new circuits. 2018 IBC section 107

3) Sheet P1.0 (Plumbing Drawings): Include the water supply piping/tubing diagrams and details to the beverage machines. Show the floor sink traps with the DWV piping diagrams. 2018 IBC section 107, 2018 IPC section 1002



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/15/2023 5:01:02 PM
See building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/15/2023 5:01:23 PM
See building review comments.
08/13/2023 Fire New Construction REVIEW COMPLETED
08/10/2023 PDSD Application Completeness Express REVIEW COMPLETED