Permit Number: TC-COM-0823-01958
Parcel: 14111030B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-01958
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/07/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/6/2023 8:46:18 AM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/6/2023 8:44:50 AM
Only one revised sheet was submitted. The file named "TCCOM082301958 - Tie-Downs - Amtex Installation Manual_v1" only includes the responses to the review comments.

1) Resolved - Sheet A0.0 (Cover Sheet): Include the allowed vs actual area, height, and number of stories. (2018 IBC Chapter 5)

2) Unresolved - Sheet P1.1 (Underground Plumbing Drawings): The underground sewer and water main piping are shown under the building support piers shown on sheet #9. The piping depth is not detailed. Please revise the plans based on the
final foundation plans to be submitted. (2018 IPC section 305) No revised plans submitted.

3) Unresolved - Sheet #7 (Elevation Views): An accessible building entrance and steps are not shown on the elevation views. Please revise all affected sheets. (2018 IBC sections 1106, 1011, 1012, 1014) No revised plans submitted.

4) Unresolved - Sheet #9 (Foundation Drawing): The foundation pier drawing is noted that it is for reference only and a separate site-specific installation plan is required. Please submit a geotechnical engineer report and foundation plans
including the anchoring/tie-down drawings. (2018 IBC sections 107, 1803) The foundation shown in the structural calculations still includes 2500psf soil bearing capacity was used in addition to 1000psf note. Please coordinate the architectural/structural details and submit the final foundation construction drawings with all pier/footing dimensions and details. Include the anchoring/tie-down drawings.



Mechanical N/A



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/6/2023 8:45:23 AM
See the building review comments



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/6/2023 8:46:00 AM
See the building review comments.
11/03/2023 PDSD Application Completeness Express REVIEW COMPLETED