Permit Number: TC-COM-0823-01958
Parcel: 14111030B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-01958
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2023 Site Zoning APPROVED
09/13/2023 Water - PDSD APPROVED
08/13/2023 Fire New Construction NOT REQUIRED
08/17/2023 Site Engineering NOT REQUIRED
09/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/17/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/17/2023 12:09:28 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/17/2023 12:04:11 PM
1) Sheet A0.0 (Cover Sheet): Include the allowed vs actual area, height, and number of stories. (2018 IBC Chapter 5)

2) Sheet P1.1 (Underground Plumbing Drawings): The underground sewer and water main piping are shown under the building support piers shown on sheet #9. The piping depth is not detailed. Please revise the plans based on the final foundation plans to be submitted. (2018 IPC section 305)

3) Sheet #7 (Elevation Views): An accessible building entrance and steps are not shown on the elevation views. Please revise all affected sheets. (2018 IBC sections 1106, 1011, 1012, 1014)

4) Sheet #9 (Foundation Drawing): The foundation pier drawing is noted that it is for reference only and a separate site specific installation plan is required. Please submit a geotechnical engineer report and foundation plans including the anchoring/tie-down drawings. (2018 IBC sections 107, 1803)



Mechanical N/A




Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/17/2023 12:08:40 PM
See the building review comments.




Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/17/2023 12:09:09 PM
See the building review comments.
08/11/2023 PDSD Application Completeness Express REVIEW COMPLETED