Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0823-01957
Parcel: 138244270

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-01957
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2023 Site Zoning APPROVED
09/15/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/05/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 9/2/2023 3:37:57 AM



Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 9/2/2023 3:36:48 AM
General comment- Verify the actual cost for the project, the application indicates 95,000.00 which appears to be low based on the submitted drawings.

General comment- Please be advised that the engineering stamp is set to expire at the end of the month.

G1.001- The drawing index includes the civil drawings which were not provided with the set. Provide the complete set or remove the civil drawings from the index.

G1.001- Update the applicable codes to indicate the 2018 International Plumbing Code.

A1.101- Provide a minimum of 18” on the latch side for door 4 from the equipment rm to the service bays. ICC A117.1-2009 Figure 404.2.3.2. Spaces and elements within employee work areas shall be constructed so that individuals with disabilities
can approach, enter, and exit the work area. 2018 IBC 1103.2.2.

A1.101- Provide details or notes indicating the minimum requirements for the new alternating tread stair. Note 16 indicates a specific manufacturer, however it is unknown if the device specified meets the minimum standards of 2018 IBC 1011.14.

A1.102- Clarify the distance from the top of the alternating stair to the wall at the top on the attic level floor plan. There is a minimum of 2’-11” is noted on the sides of the stair guards however the clear landing at the top is unknown.

A3.101- the building sections indicate that the attic storage area is to have a clear floor to ceiling height of 4’-7 ½”. To be used for storage, a minimum of not less than 7 feet is to be provided. Modify the drawings or remove the storage and occupancy from this area. 2018 IBC 1207.2.




Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 9/2/2023 3:37:40 AM
M1.01- Provide mechanical ventilation in the area in the service bays, all repair garages shall be “mechanically ventilated” in accordance with the IMC and not just naturally ventilated through the open garage bay doors. There is no way of knowing
that all of the bay doors will be open at all times when there are vehicles in the building. 2018 IBC 406.8.1.

M1.01- Indicate the location of the gas detection system on the drawings. A gas detection system shall be provided to detect leakage of non-odorized gaseous fuel including in the service pits. in accordance with 2018 IBC 406.8.2.



Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 9/2/2023 3:37:18 AM
E1.01- Provide an occupancy sensor for the attic storage room lighting plan. Occupancy sensors are required in storage rooms and other spaces 300 sf or less. 2018 IECC C405.2.1.

E1.01- Provide a service receptacle in the attic area for the servicing of the water heater. A receptacle outlet shall be located on the same level and within 25 feet of the equipment. 2017 NEC 210.63



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 9/2/2023 1:08:35 PM
First Plumbing review:
1). On plan page G1.001-update the applicable codes to indicate the 2018 International Plumbing Code.

2). add Primary & overflow scupper detail to plan page A1.102, to show these are separate through wall scuppers at different heights. also if primary became blocked at parapet wall the separate secondary scupper is able to function independently.
That isn't clear on detail 1 roof plan. -IPC 1106.5 , 1108

3). Plan submittal to be accompanied by the civil site utility piping plan for the continuation the water service & sewer as stated on plan page P1.01 -IPC 106.3.1

4). Lavatory faucet on plan page P0.01 needs to be the automatic type- Tucson plumbing code amendment 419.6

5). Add fixture spacing measurements to plan page P1.01 -IPC 404.2, 405.3.1

6). Does air compressor require a hub drain for periodic discharge? if yes add to plans -IPC 106.3.1
08/23/2023 Site Engineering REQUIRES RESUBMIT 1. The provided roof plan does not match the roof plan on the approved development package. Please either provide a matching construction set or revise the development package to match the provided construction documents.

Lianne Evans
lianne.evans@tucsonaz.gov
09/15/2023 Water - PDSD REQUIRES RESUBMIT Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
08/25/2023 Fire New Construction REVIEW COMPLETED
08/17/2023 PDSD Application Completeness REVIEW COMPLETED