Permit Number: TC-COM-0823-01954
Parcel: 12305215A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0823-01954
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/17/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 1/16/2024 10:11:12 AM
Structural review is approved. Subject to the field inspector's approval.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 1/16/2024 10:04:34 AM
1) Unresolved - Sheet G001 (Cover Sheet): Include the actual vs allowable area, height, and number of stories per 2018 IBC Chapter 5. The total building area is to include the patio dining area. 2018 Chapter 2 Building Area and Fire Area definitions.
Please detail if fire alarms are installed. The allowable area, height, and number of stories specified do not meet the limitations detailed in 2018 IBC Tables 504.3, 504.4, 506.2 for A-2 occupancy and non-sprinklered construction type V-B. The building data cannot reference the details in a set of plans under a different permit. Please include the building data in this set of plans. Include the sprinkler and fire alarm (if being installed) plans in the deferred submittal list. The occupant load
calculations are to include the exterior dining area and the areas used for refrigeration, food display cases, dishwashing, ice machines, hand wash sinks, etc. are to be included in the kitchen load calculations. Please revise and coordinate all affected sheets and details (several locations of load calculations).

2) Unresolved - Sheet G002 (Life Safety & Plumbing Fixture Calculations) and G002.1 (Occupancy Load Plan): Floor areas have not been included in the occupancy calculations. The entire floor area for assembly use is to be used to determine the occupant load of this space using the occupant load factor of 1/15sf for areas with tables and chairs and 1/5sf for standing areas which include the floor spaces that do not have tables or chairs such as the sales, waiting, and lobby areas. The condiment station is not a mercantile use. Fixed seating is calculated per 2018 IBC section 1004.6. The "Workroom" is part of the "Beverage Prep" areas are to use 1/200sf factor for commercial kitchen occupancy. The office is 1/150sf and the break room is 1/15sf. The patio dining area is also to be used in the occupancy calculations at 1/15sf. Please revise all affected sheets. (2018 IBC Table 1004.5, sections 1004, 1004.5, 1004.6 for fixed seating, Sprinklers are required when the number of occupants exceeds 99 per 2018 IBC section 903.2.1.2. If sprinklers are being installed, correct the notes and deferred submittals on sheet G001. Please revise and coordinate all affected sheets and details (several locations of load
calculations). Show the revised total occupants under "Occupancy Load" on sheet G001. The occupant load calculations are to include the exterior dining area and the areas used for refrigeration, food display cases, dishwashing, ice machines, hand
wash sinks, etc. are to be included in the kitchen load calculations.

3) Resolved - Sheet A005 (Patio Plans): Construction plans for the patio roof, support columns, footings, and roof drainage were not included in the plans. (2018 IBC section 107) Please specify on the plans that the structural plans for the covered patio were submitted in a separate permit already issued.

4) Resolved - Sheet P-102 (Plumbing Drawings): Include the Drainage Fixture Unit calculations. (2018 IPC section 106.3.1)

5) Resolved - Sheet P-401 (Plumbing Diagram): Please include the individual fixture waste pipe sizes. (2018 IPC section 106.3.1)

6) Resolved - Sheets P-102, P-401: There are several hand sinks that do not drain into the grease interceptor. 2018 IPC amended section 1003.3 requires the hand sinks to be connected to the grease interceptor or have a sign posted above them
stating: “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.”

7) Resolved - Sheet E-101 (Electrical Power Plans): Receptacles in the break room and kitchen within 6ft of sinks are not shown as being GFCI protected. (2017 NEC section 210.8(B))

8) Resolved - Sheet E-102 (Electrical Lighting Plans): Lights are not shown in the patio dining area. (2018 IBC Section 1008.2) Please revise all affected pages.




Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 1/16/2024 10:09:40 AM
Mechanical review is approved. Subject to the field inspector's approval.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 1/16/2024 10:07:04 AM
Pending the final occupant load calculations, sprinkler, and fire alarm details.
1) Unresolved - Sheet G001 (Cover Sheet): Include the actual vs allowable area, height, and number of stories per 2018 IBC Chapter 5. The total building area is to include the patio dining area. 2018 Chapter 2 Building Area and Fire Area definitions.
Please detail if fire alarms are installed. The allowable area, height, and number of stories specified do not meet the limitations detailed in 2018 IBC Tables 504.3, 504.4, 506.2 for A-2 occupancy and non-sprinklered construction type V-B. The building data cannot reference the details in a set of plans under a different permit. Please include the building data in this set of plans. Include the sprinkler and fire alarm (if being installed) plans in the deferred submittal list. The occupant load
calculations are to include the exterior dining area and the areas used for refrigeration, food display cases, dishwashing, ice machines, hand wash sinks, etc. are to be included in the kitchen load calculations. Please revise and coordinate all affected sheets and details (several locations of load calculations).

2) Unresolved - Sheet G002 (Life Safety & Plumbing Fixture Calculations) and G002.1 (Occupancy Load Plan): Floor areas have not been included in the occupancy calculations. The entire floor area for assembly use is to be used to determine the occupant load of this space using the occupant load factor of 1/15sf for areas with tables and chairs and 1/5sf for standing areas which include the floor spaces that do not have tables or chairs such as the sales, waiting, and lobby areas. The condiment station is not a mercantile use. Fixed seating is calculated per 2018 IBC section 1004.6. The "Workroom" is part of the "Beverage Prep" areas are to use 1/200sf factor for commercial kitchen occupancy. The office is 1/150sf and the break room is 1/15sf. The patio dining area is also to be used in the occupancy calculations at 1/15sf. Please revise all affected sheets. (2018 IBC Table 1004.5, sections 1004, 1004.5, 1004.6 for fixed seating, Sprinklers are required when the number of occupants exceeds 99 per 2018 IBC section 903.2.1.2. If sprinklers are being installed, correct the notes and deferred submittals on sheet G001. Please revise and coordinate all affected sheets and details (several locations of load
calculations). Show the revised total occupants under "Occupancy Load" on sheet G001. The occupant load calculations are to include the exterior dining area and the areas used for refrigeration, food display cases, dishwashing, ice machines, hand
wash sinks, etc. are to be included in the kitchen load calculations.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 1/16/2024 10:10:25 AM
Pending the final occupant load calculations, sprinkler, and fire alarm details.
1) Unresolved - Sheet G001 (Cover Sheet): Include the actual vs allowable area, height, and number of stories per 2018 IBC Chapter 5. The total building area is to include the patio dining area. 2018 Chapter 2 Building Area and Fire Area definitions.
Please detail if fire alarms are installed. The allowable area, height, and number of stories specified do not meet the limitations detailed in 2018 IBC Tables 504.3, 504.4, 506.2 for A-2 occupancy and non-sprinklered construction type V-B. The building data cannot reference the details in a set of plans under a different permit. Please include the building data in this set of plans. Include the sprinkler and fire alarm (if being installed) plans in the deferred submittal list. The occupant load
calculations are to include the exterior dining area and the areas used for refrigeration, food display cases, dishwashing, ice machines, hand wash sinks, etc. are to be included in the kitchen load calculations. Please revise and coordinate all affected sheets and details (several locations of load calculations).

2) Unresolved - Sheet G002 (Life Safety & Plumbing Fixture Calculations) and G002.1 (Occupancy Load Plan): Floor areas have not been included in the occupancy calculations. The entire floor area for assembly use is to be used to determine the occupant load of this space using the occupant load factor of 1/15sf for areas with tables and chairs and 1/5sf for standing areas which include the floor spaces that do not have tables or chairs such as the sales, waiting, and lobby areas. The condiment station is not a mercantile use. Fixed seating is calculated per 2018 IBC section 1004.6. The "Workroom" is part of the "Beverage Prep" areas are to use 1/200sf factor for commercial kitchen occupancy. The office is 1/150sf and the break room is 1/15sf. The patio dining area is also to be used in the occupancy calculations at 1/15sf. Please revise all affected sheets. (2018 IBC Table 1004.5, sections 1004, 1004.5, 1004.6 for fixed seating, Sprinklers are required when the number of occupants exceeds 99 per 2018 IBC section 903.2.1.2. If sprinklers are being installed, correct the notes and deferred submittals on sheet G001. Please revise and coordinate all affected sheets and details (several locations of load
calculations). Show the revised total occupants under "Occupancy Load" on sheet G001. The occupant load calculations are to include the exterior dining area and the areas used for refrigeration, food display cases, dishwashing, ice machines, hand
wash sinks, etc. are to be included in the kitchen load calculations.
01/11/2024 PDSD Application Completeness REVIEW COMPLETED