Permit Number: TC-COM-0823-01953
Parcel: 11205001A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0823-01953
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/25/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The resubmitted plan documents did not include a scope of electrical work narrative as requested in the previous plan review. The scope of work simply states,” COURTYARD IMPROVEMENTS PAVING SHADE STRUCTURE PLAY GROUND EQUIPMENT LANDSCAPE IRRIGATTION”. No mention of scope of power and lighting. For clarity, please provide a detailed scope of work narrative.

2 The power and lighting shown on the site plans and details is insufficient to verify a safe and code compliant electrical installation.

2a. Provide a complete luminaire schedule.

2b. Provide manufacturer cut sheets of the new proposed exterior luminaires with highlighted identification in the specs of the luminaire model, and color temperature output selected for this project and correlate with the luminaire schedule. OLC section 104.2(2)

2c. Show the locations of all the luminaires (80) as shown in the Lumen Lighting Ordinance Calculations including existing to remain and identify them with a mark that correlates with the Lighting Ordinance Calculations and the luminaire schedule. OLC section 104.2(1).

3 Identify the new branch circuits in the panel schedule. NEC 408.4

4 Verify that the new Time Clock is listed as a raceway for accommodating the 120volt receptacle branch circuits and a total of 7 #10 AWG conductors. Please provide the manufacturers cut sheet of specifications. NEC 110.3

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code (OLC).
05/24/2024 PDSD Application Completeness Express REVIEW COMPLETED