Permit Number: TC-COM-0823-01927
Parcel: 11012094F

Address:
5301 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-01927
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2023 Site Zoning APPROVED
09/11/2023 Water - PDSD APPROVED
08/15/2023 Site Engineering NOT REQUIRED
09/11/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/15/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/15/2023 3:26:20 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 8/15/2023 3:25:43 PM
1) General: Include the energy code compliance details meeting the envelope requirements of 2018 IECC section C402.

2) Sheet G0.0 (Cover Sheet): Include the occupancy group classification, construction type, occupant load of lower level using the means of egress, codes and wind loads used in the design. 2018 IBC section 107.

2) Sheet A2.1: Show the ramp slope, vertical rise height, width, and railing meeting the means of egress requirements of 2018 IBC section 1012.

3) Sheet S3.1: Section details do not include the framing lumber sizes and the sheathing plywood type and thickness. The porch rafters are shown being spaced 32" o.c. which exceeds the spacing limits of 2018 IBC section 2308.7.2, include the
sheathing details in the section views and structural calculations.

4) Sheet S2.1: Include foundation dimensions on the foundation plans or detail the sheet number and detail where the design details can be found. The porch footings do not specify where to find the dimensions and the other notes reference the sections on Sheet S3.1 but the sections do not provide the concrete, framing, and lumber dimensions or reference the sheets that have the details.

5) Sheet S2.1 and A1.1: Include the work area and structure dimensions on the proposed structure. 2018 IBC section 107.


Mechanical N/A



Electrical N/A


Plumbing N/A
08/13/2023 Fire New Construction REVIEW COMPLETED
08/08/2023 PDSD Application Completeness REVIEW COMPLETED