Permit Number: TC-COM-0823-01925
Parcel: 12509012A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-01925
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/07/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 11/3/2023 8:48:02 PM
1. UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments.

2. S0.01 - DESIGN ASSUMPTIONS: The following structural design information shall be included in the construction documents per 2018 IBC Section 1603. Please include the following items in the structural general notes.

i. Wind design data: Design wind pressures for exterior component and cladding materials, psf

ii. Seismic design data

a. Seismic design category

b. Basic seismic-force resisting system(s) for new canopies

c. Response modification coefficient(s), R

d. Analysis procedure used
iii. Geotechnical Information: Design assumptions for retaining walls (active/passive soil pressure, coefficient of friction)

3. S1.03 - MISSING INFORMATION: Please specify a minimum embedment for all anchors specified in the Ledger Schedule on Sheet S1.03. If preferred, it is acceptable to include the minimum embed information on the individual framing details that show post-installed ledgers.

4. S4.01 - MISSING INFORMATION: In Detail 106 on Sheet S4.01, specify how the sill plates of new wood stud walls shall be anchored to the foundations. Include minimum fastener size, embedment and maximum spacing.

5. S5.01 - MISSING INFORMATION: In Details 213 & 224, confirm how the proposed HSS canopy beams are being spliced. If beams are being field welded, please provide a minimum weld size.

6. S5.01 & S5.02 - MISSING INFORMATION: Where framing details shown a new hot-rolled steel beam supported with post-installed anchors into an existing masonry or concrete wall (Details 218, 221 & 227), specify a minimum embedment length for proposed epoxy anchors.

7. S5.02 - MISSING INFORMATION: On details showing the new CMU parapet extension, please provide a minimum embedment length for grouted reinforcement (Details 228 & 235).



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 8/11/2023 7:27:14 PM




Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Approved with Comments
Reason:
Date Completed : 8/13/2023 7:21:27 PM
No mechanical plans submitted no action required from mechanical




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 8/22/2023 8:25:22 AM
Electrical Review of Grey Shell
By: Ron Ross PE
E2.02 FEEDER DIAGRAMS: Font issues with PDF or AutoCAD for a couple of notes.

E2.03 PANEL SCHEDULES & DETAILS: Font issues with PDF or AutoCAD for a couple note on Schematic Feeder Wiring Diagram.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 11/3/2023 6:19:27 AM
Second Plumbing Review:
1). Resolved- Hose bibs on plan pages P1.00 & P1.01 need shut off valves-IPC 606.2

2). Resolved- Revise gas notes 11 on plan page P1.00 & P1.01 to state future gas will be capped in ceiling space-IFGC 404.15

3). Resolved- Show or notate the sanitary vent be piped or connecting to a vent the extends to the exterior on plan pages P1.00 & P1.01-IPC 904.3
11/22/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
11/22/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-0823-01925
2545 E BROADWAY BL Zoning C-1/R-2
Solot Redevelopment

TRANSMITTAL DATE:‎November 22, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This comment is still applicable.
1. Zoning has reviewed the building plans for compliance with the associated development package TD-DEV-0423-00202. Although it appears the building plan footprint, building height, and square footage are consistent with the submitted development package, Zoning cannot approve the building plans until all review agencies have approved TD-DEV-0423-00202. Please note that the proposed shade canopy within the vehicular use area is not depicted on the development package drawings. The canopy is required to be included within the scope of work of the development package to be approved under TC-COM-0823-01925.


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
10/30/2023 PDSD Application Completeness REVIEW COMPLETED