Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Approved
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0823-01905
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/11/2023 | Bldg Permits - Post Review | REVIEW COMPLETED | |||
09/11/2023 | External Reviewers - SAFEBuilt | REVIEW COMPLETED | Structural(S) Reviewer Daljit Benipal dbenipal@safebuilt.com Conditionally Approved Reason: Date Completed : 8/16/2023 4:58:26 PM NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 8/11/2023 10:52:01 AM Mechanical N/A Electrical N/A Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Conditionally Approved Reason: Date Completed : 9/9/2023 9:48:58 AM Second plumbing Review: OK SUBJECT TO FIELD INSPECTIONS 1). Resolved-the dog mister listed on plan CL-8 needs a detail added to plan page LD-2 -IPC 106.3.1 2). Resolved-the playground drinking fountain listed on CL-4 needs a detail added to plan page LD-2 -IPC 106.3.1 3). RESOLVED-add fixture schedule with manufacturer names & model numbers of the misters fountains shown on plan pages CL-4 & CL-8 - IPC 303 ** Based on product specifications on their respective web pages, the Pet fountain incorporates an internal backflow device, the Mister water outlets are located at a level to comply with an acceptable means of Air gap for backflow protection** 4). Resolved-Provided Tucson park ordinance that allows park fountains to discharge to earth. -IPC 301.3** PIMA County & Parks detail added to plan page LD-2 and detail submitted with document upload 5). Now that water connected equipment details have been added to Page LD-2 , All water connections at each device/appliance/apparatus will need an individual shut off valve- IPC 606.2 =Subject to field inspections** |
||
09/08/2023 | PDSD Application Completeness | REVIEW COMPLETED |