Permit Number: TC-COM-0823-01898
Parcel: 12602033B

Address:
990 N BENTON AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-01898
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2023 Site Engineering APPROVED
08/10/2023 Site Zoning APPROVED
09/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/14/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 8/13/2023 1:39:27 AM
1. Sheet S-1 – Provide the scope of special inspections and tests compliance with 2018 International Building Code Chapter 17: Statements (part 1704.3) and schedule (part 1704.2.3).



Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 8/13/2023 1:41:00 AM
1. Sheet G1 – Provide existing/demolition site plan. Aerial plan appears to show an existing shed so what is the scope of the

existing building? Is it removing existing car port?
2. Sheet G1 – List the applicable building codes within your scope of work.
City of Tucson IBC Local Amendments
• Amendments to the 2018 International Building Code
• Amendments to the 2018 International Energy Conservation Code
• Amendments to the 2018 International Fuel Gas Code
• Amendments to the 2018 International Mechanical Code
• Amendments to the 2018 International Plumbing Code
• Amendments to the 2017 National Electrical Code
• Amendments to the 2018 International Fire Code
• City of Tucson/Pima County Outdoor Lighting Code
• ICC A117.1 - 2009 Accessible and Usable Buildings and Facilities (by reference)
Adopting Local Amendments to the Building Code is authorized by Ordinance #11590.
3. Sheet G1 – Provide life safety plan showing compliance with 2018 International Building Code chapter 10 such as occupancy load calculation, number of egresses, exit distance and door width.
4. Sheet G1 – Provide building code analysis compliance with 2018 International Building Code such as occupancy classification (Is it S-2?), building height, building area and building type (Is it V-B)?
5. Sheet G1 – What are the scopes of fire sprinkler system (NFPA 13) and fire alarm system (NFPA 72)?
6. Sheet G1 – Any deferred submittals or separate permits?
7. Show insulation values of roof and walls in compliance with the building envelope requirements per 2018 International Energy Conservation Code section C402.
8. Sheet A2 – Show complete exterior elevations: Missing South and East elevations. Show complete cisterns. North elevation shows one cistern unlike cisterns shown in floor plan.
9. Sheet A2 – Show the parking paint and curb in the floor plan. Electrical sheet plan shows 6 parking space. Any curb detail?
10. Sheet A2 – Locate the portable fire extinguisher required in 2018 IBC section 906.



Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 8/13/2023 1:40:13 AM
1. Provide the scope and design of ventilation method compliance with 2018 International Mechanical Code. Is it accordance with section 402 natural ventilation or 403 mechanical ventilation? How does it comply with enclosed parking garages section 404? Does it meet ventilation area required per section 402.2?



Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 8/13/2023 1:40:29 AM
1. 2018 IECC section C405.2.1 states Occupancy sensor controls shall be installed to control lights in the following space types: 8. Storage rooms; 11. Warehouse storage areas.


Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 8/13/2023 1:39:51 AM
1. Provide minimum plumbing facilities accordance with 2018 International Plumbing Code section 403. Show required fixture calculations and provided fixture count such as water closets, lavatories, drinking fountain and service sink.
2. Show the scope of accessible plumbing facilities per section 2018 IPC 404 that accessible parking is shown in site plan.
3. What is the purpose of the 42” diameter cisterns? Are they for landscape irrigation system?
09/07/2023 Water - PDSD REQUIRES RESUBMIT Provide the location and size of the water meter and backflow prevention assembly to support the minimum required plumbing fixtures, Show the size, material, and route of the water service line to the building. Reference: Section 602.1, IPC 2018.
08/13/2023 Fire New Construction REVIEW COMPLETED
08/04/2023 PDSD Application Completeness Express REVIEW COMPLETED