Permit Number: TC-COM-0823-01898
Parcel: 12602033B

Address:
990 N BENTON AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-01898
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2023 Water - PDSD NOT REQUIRED
10/26/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/04/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 10/1/2023 3:56:43 AM
2. Pending clarification of specific occupant use requirements. (associated building review comment 3).




Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 10/1/2023 3:57:58 AM
3. Sheet G1 – Provide life safety plan showing compliance with 2018 International Building Code chapter 10 such as occupancy load calculation, number of egresses, exit distance and door width.

Sheet G1 shows use classification as “storage group ‘S’” however states that occupancy load is not applicable. Provide exception section per 2018 International Building Code (IBC) such determination. Be specific in the type of storage group
accordance with 2018 IBC section 311 which requires that all structures (or parts thereof) designed or occupied for the storage of moderate- and low-hazard materials are to be classified either Group S-1 (moderate hazard) or S-2 (low hazard). Furthermore, “Parking garages, open or enclosed” is listed in section 311.3 Low-hazard storage, Group S-2. “Motor vehicle repair garage…” is listed as Group S-1.

2018 IBC section 1004 determines occupant load for means of egress requirements and “Parking garages” listed in Table 1004.5 with occupant load factor of 200 gross.

Is this a “Private garages” which is listed in 2018 IBC section 312 utility and miscellaneous group U? Use/intent of this facility should be clearly stated. Is it for a business like car repair shop, rented out garage space, etc.? Or is it a private individual garage?

4. Sheet G1 – Provide building code analysis compliance with 2018 International Building Code such as occupancy classification (Is it S-2?), building height, building area, and building type (Is it V-B)?

Clarify specific occupant use requirements (associated building review comment 3).

5. Sheet G1 – What are the scopes of fire sprinkler system (NFPA 13) and fire alarm system (NFPA 72)?

Clarify specific occupant use requirements (associated comment 3) which determines fire protection systems.

7. Show insulation values of roof and walls in compliance with the building envelope requirements per 2018 International Energy Conservation Code (IECC) section C402. Registered design professional response states “not required for storage
building” so provide the building code section states this exception.

9. Sheet A2 – Show the parking paint and curb in the floor plan. Electrical sheet plan shows 6 parking space. Any curb detail? Coordinate the discrepancy of parking layout paint on electrical and architectural sheets.



Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 10/1/2023 3:55:47 AM
1. Provide the scope and design of ventilation method compliance with 2018 International Mechanical Code. Is it accordance with section 402 natural ventilation or 403 mechanical ventilation? How does it comply with enclosed parking garages section 404? Does it meet ventilation area required per section 402.2?

Pending clarification of specific occupant use requirements (associated building review comment 3).




Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 10/1/2023 3:54:57 AM
1. 2018 IECC section C405.2.1 states Occupancy sensor controls shall be installed to control lights in the following space types: 8. Storage rooms; 11. Warehouse storage areas.

Clarify specific occupant use requirements (associated building review comment 3). Registered design professional response states it’s an “accessory use.” Provide this applicable code section that dictates this accessory use. 2018 IBC section 508.2 states accessory occupancies for mixed use and occupancy.



Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 10/1/2023 3:56:17 AM
1. Provide minimum plumbing facilities accordance with 2018 International Plumbing Code section 403. Show required fixture calculations and provided fixture count such as water closets, lavatories, drinking fountain and service sink.

Clarify specific occupant use requirements (associated building review comment 3).

2. Show the scope of accessible plumbing facilities per section 2018 IPC 404 that accessible parking is shown in site plan.

Clarify specific occupant use requirements (associated building review comment 3)
09/28/2023 PDSD Application Completeness Express REVIEW COMPLETED