Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0823-01873
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2023 | Site Engineering | APPROVED | |||
| 08/09/2023 | Site Zoning | APPROVED | |||
| 08/13/2023 | Fire New Construction | NOT REQUIRED | |||
| 09/06/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/30/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Provide complete electrical site lighting plans design and calculations by an Arizona Registrant. Include complete compliance with the City of Tucson Outdoor Lighting Code. See section 104 for Plans and permit submittal requirements. DP plans not acceptable for construction of site lighting. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
||
| 09/06/2023 | Commercial Structural | REQUIRES RESUBMIT | 1. Submit an image of the light pole being installed, submit the specification for the light source to include the lumens as well as the kelvin temperature of the light source. If shielding is required, submit that information as well. 2. On the Lighting Plan, clearly identify/label the light poles being installed. 3. Please resubmit. |
||
| 08/07/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |