Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0726-01218
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2026 Site Zoning Standard APPROVED REF: Master Plan Set TC-COM-0726-01217
08/25/2026 Water - PDSD Standard APPROVED
08/25/2026 Commercial Mechanical Standard NOT REQUIRED
08/25/2026 Commercial Plumbing Standard NOT REQUIRED
08/19/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
08/05/2026 Site Engineering Standard NOT REQUIRED
08/25/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/25/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please amend the plans to show that all through-penetrations and membrane penetrations of fire-resistance-rated assemblies are protected with approved firestopping systems. Provide detail drawings on the plans identifying the specific UL-listed (or equivalent) firestopping systems for pipe, conduit, and duct penetrations through rated walls, floors, and ceilings (e.g., putty pads, firestop sealants, collars, or sleeves, as applicable).Per 2024 IBC Section 714.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/19/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01217 (201 W BLACKLIDGE DR Unit:BLDG 2 UNIT 117 TUCSON, AZ 85705) (Master)

Note
MASTER PLAN SET/TC-COM-0726-01217, UNIT 117, FOR THIS SHARED PLAN SET, TC-COM-0726-01220/UNIT 218, TC-COM-0726-01219/UNIT 217, TC-COM-0726-01218/UNIT 118

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide GFCI protection for all kitchen receptacles, including the Range and Fridge, per NEC 210.8(A)(6) & 210.8(D)(8). Shall be readily accessible, per NEC 210.8, and may require GFCI breakers.
2. Show locations of each smoke alarm, [NFPA 72]. Must be inside each bedroom and in the immediate vicinity outside the bedrooms. Notate that all smoke alarms must be interconnected with a power source from the building wiring and be equipped with battery backup.
3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, NEC [210.52(C)(1)] and NEC [210.52(B)(1)]. GFCI protected, NEC [210.8(A)(6)]. (missing required 2 circuits in each panel/apartment. Panel B shows only a 15A kitchen circuit. Undersized).
4. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, NEC [210.11(C)(3)] and NEC [210.52(D)].
5. Provide AFIC for all electrical outlets as listed in NEC 210.12(B). This includes kitchen outlets.
6. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
7. Provide complete compliance with the 2018 IECC for the interior lighting, including sensors and lighting controls as required. (typically COMcheck.).
8. Panelboards shall not be located in the bathroom NEC 240.24(E). Show Sub-panel ‘B’ in code compliant location.
9. Provide Surge Protection as required per 2023 NEC 230.67, NEC 230.67(D).

>>> Clarify if Units 218, 217, 118 have electrical work, or if they need only electrical clearance and no new work is being done in these units.
08/17/2026 Fire New Construction Standard REVIEW COMPLETED
08/05/2026 PDSD Application Completeness Express REVIEW COMPLETED