Permit Number: TC-COM-0726-01199
Parcel: 12701005D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0726-01199
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2026 Site Zoning APPROVED
08/13/2026 Water - PDSD APPROVED
07/31/2026 Site Engineering NOT REQUIRED
08/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/11/2026 Commercial Building REQUIRES RESUBMIT August 11, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Rd
Tucson, AZ 85712

Re: 5151 E. BROADWAY SUITE 1180
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0726-01199
Stantec Project Number: 185215066
Stantec File Number: TUC-26-044

Plan review for the project referenced above has been completed. This letter reflects comments to be addressed. PLEASE send all responses to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B I-A 1,476 10 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and signage.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2024 IBC Sec. 903] and fire alarm system [2024 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). This comment applies to this project because space is being reconfigured.

2. Please provide a written scope of work on the plans.

3. Please show all existing fire rated assemblies on the plan. Clearly show egress path from the suite to the nearest building exit.

4. It appears that one suite is being divided into two suites. Please confirm, and if that is the case, please state that on the plans in the requested “scope of work”.

5. Provide a signage plan and details demonstrating that office identification signage and other signage identifying permanent rooms or spaces will be compliant with [ICC/ANSI A117.1-2017 Sec. 703 and 2024 IBC Sec. 1112.6].

Sheet G1

1. General Notes item 12 states that all insulation shall comply with the 2012 IBC, the City of Tucson has adopted the 2024 IBC. Please correct the notes on the drawing to reflect the current code.

Sheet A1

1. Please provide a dimension for the placement of the entry door to the suite. Doors are required to have 18” maneuvering clearance on the pull side of the door. [ICC/ANSI A117.1 Sec. 404.2.3.5]

MECHANICAL COMMENTS

Sheet M1

1. Outside Air Notes: Balancing will be required, please change the note that states otherwise.

Sheet M2

1. Mechanical Notes 1.01: The City of Tucson has adopted the 2024 IECC. Please change the reference on the plans from the 2018 IECC to the 2024 IECC.

PLUMBING COMMENTS

Sheet P2

1. Please provide the total developed length for the vent for the breakroom sink. [2024 IPC Sec 906.1]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Sherryn Hensley
Senior Plan Examiner
480-687-6082
sherryn.hensley@stantec.com
08/11/2026 Commercial Electrical REQUIRES RESUBMIT August 11, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Rd
Tucson, AZ 85712

Re: 5151 E. BROADWAY SUITE 1180
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0726-01199
Stantec Project Number: 185215066
Stantec File Number: TUC-26-044

Plan review for the project referenced above has been completed. This letter reflects comments to be addressed. PLEASE send all responses to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B I-A 1,476 10 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and signage.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2024 IBC Sec. 903] and fire alarm system [2024 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). This comment applies to this project because space is being reconfigured.

2. Please provide a written scope of work on the plans.

3. Please show all existing fire rated assemblies on the plan. Clearly show egress path from the suite to the nearest building exit.

4. It appears that one suite is being divided into two suites. Please confirm, and if that is the case, please state that on the plans in the requested “scope of work”.

5. Provide a signage plan and details demonstrating that office identification signage and other signage identifying permanent rooms or spaces will be compliant with [ICC/ANSI A117.1-2017 Sec. 703 and 2024 IBC Sec. 1112.6].

Sheet G1

1. General Notes item 12 states that all insulation shall comply with the 2012 IBC, the City of Tucson has adopted the 2024 IBC. Please correct the notes on the drawing to reflect the current code.

Sheet A1

1. Please provide a dimension for the placement of the entry door to the suite. Doors are required to have 18” maneuvering clearance on the pull side of the door. [ICC/ANSI A117.1 Sec. 404.2.3.5]

MECHANICAL COMMENTS

Sheet M1

1. Outside Air Notes: Balancing will be required, please change the note that states otherwise.

Sheet M2

1. Mechanical Notes 1.01: The City of Tucson has adopted the 2024 IECC. Please change the reference on the plans from the 2018 IECC to the 2024 IECC.

PLUMBING COMMENTS

Sheet P2

1. Please provide the total developed length for the vent for the breakroom sink. [2024 IPC Sec 906.1]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Sherryn Hensley
Senior Plan Examiner
480-687-6082
sherryn.hensley@stantec.com
08/11/2026 Commercial Mechanical REQUIRES RESUBMIT August 11, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Rd
Tucson, AZ 85712

Re: 5151 E. BROADWAY SUITE 1180
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0726-01199
Stantec Project Number: 185215066
Stantec File Number: TUC-26-044

Plan review for the project referenced above has been completed. This letter reflects comments to be addressed. PLEASE send all responses to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B I-A 1,476 10 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and signage.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2024 IBC Sec. 903] and fire alarm system [2024 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). This comment applies to this project because space is being reconfigured.

2. Please provide a written scope of work on the plans.

3. Please show all existing fire rated assemblies on the plan. Clearly show egress path from the suite to the nearest building exit.

4. It appears that one suite is being divided into two suites. Please confirm, and if that is the case, please state that on the plans in the requested “scope of work”.

5. Provide a signage plan and details demonstrating that office identification signage and other signage identifying permanent rooms or spaces will be compliant with [ICC/ANSI A117.1-2017 Sec. 703 and 2024 IBC Sec. 1112.6].

Sheet G1

1. General Notes item 12 states that all insulation shall comply with the 2012 IBC, the City of Tucson has adopted the 2024 IBC. Please correct the notes on the drawing to reflect the current code.

Sheet A1

1. Please provide a dimension for the placement of the entry door to the suite. Doors are required to have 18” maneuvering clearance on the pull side of the door. [ICC/ANSI A117.1 Sec. 404.2.3.5]

MECHANICAL COMMENTS

Sheet M1

1. Outside Air Notes: Balancing will be required, please change the note that states otherwise.

Sheet M2

1. Mechanical Notes 1.01: The City of Tucson has adopted the 2024 IECC. Please change the reference on the plans from the 2018 IECC to the 2024 IECC.

PLUMBING COMMENTS

Sheet P2

1. Please provide the total developed length for the vent for the breakroom sink. [2024 IPC Sec 906.1]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Sherryn Hensley
Senior Plan Examiner
480-687-6082
sherryn.hensley@stantec.com
08/11/2026 Commercial Plumbing REQUIRES RESUBMIT August 11, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Rd
Tucson, AZ 85712

Re: 5151 E. BROADWAY SUITE 1180
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0726-01199
Stantec Project Number: 185215066
Stantec File Number: TUC-26-044

Plan review for the project referenced above has been completed. This letter reflects comments to be addressed. PLEASE send all responses to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B I-A 1,476 10 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and signage.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2024 IBC Sec. 903] and fire alarm system [2024 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). This comment applies to this project because space is being reconfigured.

2. Please provide a written scope of work on the plans.

3. Please show all existing fire rated assemblies on the plan. Clearly show egress path from the suite to the nearest building exit.

4. It appears that one suite is being divided into two suites. Please confirm, and if that is the case, please state that on the plans in the requested “scope of work”.

5. Provide a signage plan and details demonstrating that office identification signage and other signage identifying permanent rooms or spaces will be compliant with [ICC/ANSI A117.1-2017 Sec. 703 and 2024 IBC Sec. 1112.6].

Sheet G1

1. General Notes item 12 states that all insulation shall comply with the 2012 IBC, the City of Tucson has adopted the 2024 IBC. Please correct the notes on the drawing to reflect the current code.

Sheet A1

1. Please provide a dimension for the placement of the entry door to the suite. Doors are required to have 18” maneuvering clearance on the pull side of the door. [ICC/ANSI A117.1 Sec. 404.2.3.5]

MECHANICAL COMMENTS

Sheet M1

1. Outside Air Notes: Balancing will be required, please change the note that states otherwise.

Sheet M2

1. Mechanical Notes 1.01: The City of Tucson has adopted the 2024 IECC. Please change the reference on the plans from the 2018 IECC to the 2024 IECC.

PLUMBING COMMENTS

Sheet P2

1. Please provide the total developed length for the vent for the breakroom sink. [2024 IPC Sec 906.1]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Sherryn Hensley
Senior Plan Examiner
480-687-6082
sherryn.hensley@stantec.com
08/14/2026 Fire New Construction REVIEW COMPLETED