Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0726-01196
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/13/2026 | Commercial Building | APPROVED | |||
| 08/06/2026 | Commercial Electrical | APPROVED | |||
| 08/12/2026 | Commercial Mechanical | APPROVED | |||
| 08/12/2026 | Water - PDSD | APPROVED | |||
| 08/13/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/12/2026 | Commercial Plumbing | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0726-01196 ADDRESS/PARCEL: 1785 W AJO WY TUCSON, AZ 85713 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. The existing fryer (shown on the demo floor plan) is being replaced. Please show all other gas-fired appliances connected to the gas meter as well and the total gas demand seen by the meter. Verify the existing gas piping system is adequately sized for the replacement fryer. Reference: Section 402, IFGC 2024. |
||
| 08/05/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 07/30/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |