Permit Number: TC-COM-0726-01195
Parcel: 134220190

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0726-01195
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/28/2026 Commercial Mechanical Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01195
ADDRESS/PARCEL: 6744 E BROADWAY BL TUCSON, AZ 85710

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Previous comment not fully addressed [Initial comment - Please provide an engineering evaluation, prepared by an Arizona registered design professional, verifying that the existing roof structure is capable of supporting the proposed rooftop HVAC units. If any modifications to the existing roof framing are required to accommodate the added load, provide complete structural design and calculations prepared and sealed by an Arizona registered engineer. Reference: 2024 IBC Section 107.2.7.]
a. Structural Sheet S2.0 does not include the engineer’s calculations or a seal from an Arizona-registered design professional.
2. Please clearly show the routing and termination of the condensate drains from the new units. Reference: Section 307.2.1, IMC 2024 as amended by the City of Tucson.
3. Please indicate the roof slope on the plans and provide details of the platform serving the rooftop mechanical equipment, including guards complying with Section 304.11 and a platform complying with Section 306.5.1 of the 2024 IMC.
10/28/2026 PDSD Application Completeness Express REVIEW COMPLETED