Permit Number: TC-COM-0726-01192
Parcel: 11451216D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0726-01192
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2026 Commercial Electrical APPROVED
08/12/2026 Commercial Mechanical APPROVED
08/12/2026 Water - PDSD APPROVED
08/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/13/2026 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01192
ADDRESS/PARCEL: (9075 E TANQUE VERDE RD TUCSON, AZ 85749)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
a. Duct horizontal run is over 10 ft. Please provide support drawing and location.
b. Please confirm proper duct slope is met complying to IMC 506.3.7
c. Please resubmit.
08/12/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01192
ADDRESS/PARCEL: 9075 E TANQUE VERDE RD TUCSON, AZ 85749

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. The existing 2-vat fryer (shown on the demo floor plan) is being replaced. Please show all other gas-fired appliances connected to the gas meter as well and the total gas demand seen by the meter. Verify the existing gas piping system is adequately sized for the replacement fryer. Reference: Section 402, IFGC 2024.
08/05/2026 Fire New Construction REVIEW COMPLETED
07/30/2026 PDSD Application Completeness Express REVIEW COMPLETED