Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0726-01176
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2026 | Commercial Mechanical Express | NOT REQUIRED | |||
| 07/30/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/29/2026 | Addressing Validation | REQUIRES RESUBMIT | For questions please contact: PDSD-Permits@tucsonaz.gov. This permit is for 929 E Fort Lowell only. You will need to apply for a separate permit for the work being done on 925 E Fort Lowell. When applying for this permit, please correct the address on the site plan from 927 E Fort Lowell to 925 E Fort Lowell (927 E Fort Lowell is not a valid address). | ||
| 07/30/2026 | Commercial Plumbing Express | REQUIRES RESUBMIT | 1. This permit is for 929 E Fort Lowell Road only. You will need to apply for a separate permit for the work being done on 925 E Fort Lowell. 2. Tucson Water records show only one 5/8” water installed for the Parcel containing 925 and 929 E Fort Lowell Road. Verify that the 5/8” water meter serving 929 E Fort Lowell Road is not also serving 925 E Fort Lowell Road. 3. The nominal ¾ inch PEX tubing is 17 mm in diameter. The water service pipe shall not be less than ¾ inch (19 mm) in diameter. Reference: Section 603.1, IPC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 07/29/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |