Permit Number: TC-COM-0726-01176
Parcel: 113043310

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0726-01176
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2026 Commercial Mechanical Express NOT REQUIRED
07/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/29/2026 Addressing Validation REQUIRES RESUBMIT For questions please contact: PDSD-Permits@tucsonaz.gov. This permit is for 929 E Fort Lowell only. You will need to apply for a separate permit for the work being done on 925 E Fort Lowell. When applying for this permit, please correct the address on the site plan from 927 E Fort Lowell to 925 E Fort Lowell (927 E Fort Lowell is not a valid address).
07/30/2026 Commercial Plumbing Express REQUIRES RESUBMIT 1. This permit is for 929 E Fort Lowell Road only. You will need to apply for a separate permit for the work being done on 925 E Fort Lowell.
2. Tucson Water records show only one 5/8” water installed for the Parcel containing 925 and 929 E Fort Lowell Road. Verify that the 5/8” water meter serving 929 E Fort Lowell Road is not also serving 925 E Fort Lowell Road.
3. The nominal ¾ inch PEX tubing is 17 mm in diameter. The water service pipe shall not be less than ¾ inch (19 mm) in diameter. Reference: Section 603.1, IPC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
07/29/2026 PDSD Application Completeness Express REVIEW COMPLETED