08/13/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01173 (3950 E IRVINGTON RD Unit:BLDG 1 TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Show Ground-Fault Protection of Equipment at the 1200A switchboard per NEC 230.93.
2. Reference Sheet EV02.1, Future Panelboard 'HEV'. Show this panel and the connected EV charging stations as 'Future' on sheet EV02.
3. Reference Sheet EV02.1, Wire Tag 2 and Sheet EV02.3, New xfmr to SES circuit. The provided conductors are undersized for the given 1200A Main Circuit Breaker and SES rating. The Wire/Conduit Sizing table on Sheet EV02.3 shoes an OCPD of 1000A used for this connection, but the panel schedule and line diagram both show a 1200 OCPD used in the SES. Correct and show consistent information and conductors rated for the actual OCPD used.
4. Reference Panelboard EV Schedule, Circuits 7,9,11, for "EV3 panelboard. This circuit shows a 400A/3P C/B. The line diagram on Sheet EV02.1 shows a 600A3P C/B. Show consistent information on each sheet.
5. Provide manufacturer's specification sheets for all Electric Vehicle Power Transfer System equipment. Show all equipment as listed, NEC 625.6.
6. Show equipment is listed for Personnel Protection per NEC 625.22.
7. Provide protection from damage and vehicular impact with bollard placement or other approved means for chargers and other equipment. NEC 300.4 Protection Against Physical Damage, NEC110.27(B) Prevent Physical Damage.