Permit Number: TC-COM-0726-01172
Parcel: 21401010A

Address:
4975 W INA RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0726-01172
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2026 Commercial Mechanical Standard APPROVED
08/27/2026 Commercial Plumbing Standard APPROVED
08/24/2026 Outdoor Lighting Standard APPROVED
08/31/2026 Site Engineering Standard APPROVED
09/01/2026 Landfill Standard NOT REQUIRED Subject project location outside of City of Tucson city limits, Landfill Ordinance is not enforced.
08/27/2026 Water - PDSD Standard NOT REQUIRED
09/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/01/2026 Commercial Post Review Express PENDING ASSIGNMENT
08/27/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01172
ADDRESS/PARCEL: (7101 N Casa Grande HWY HY Tucson, AZ 85743)
TC-COM-0526-00787 (3002 E GRANT RD Unit:UNIT 2 TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. SHEET C02 SITE OVERALL PLAN
a. Locate/identify the Existing Canopy and New Canopy over the booster pump station on the above plan drawing.
b. Locate/identify the Air Compressor Pad & Enclosure on the above plan drawing.
2. SHEET S03: Provide Structural Calculation for the Booster Pump Canopy.
3. ANTENNA
a. Provide Structural Calculation for the antenna.
4. Air Compressor enclosure.
a. Please provide construction drawings for this enclosure.
5. Electrical Building (CMU/Steel members/Metal Roof deck.
a. Please provide structural calculations.
6. Please resubmit.
08/26/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01172 (7101 N Casa Grande HWY HY Tucson, AZ 85743)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24.
2. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10.
3. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.
08/24/2026 Fire New Construction Standard REVIEW COMPLETED
08/07/2026 PDSD Application Completeness Express REVIEW COMPLETED
08/31/2026 Site Zoning Standard REVIEW COMPLETED Site is located in unincorporated Pima County and City of Tucson Zoning does not apply