Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0726-01166
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/27/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/27/2026 | Commercial Mechanical Express | REQUIRES RESUBMIT | 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacity of the unit being installed. Reference: Section C403.3.1, IECC 2024. 2. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous heat pump provided. Reference: Section C503.3, IECC 2024: If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 07/24/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |