Permit Number: TC-COM-0726-01166
Parcel: 12801005H

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0726-01166
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/27/2026 Commercial Mechanical Express REQUIRES RESUBMIT 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacity of the unit being installed. Reference: Section C403.3.1, IECC 2024.
2. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous heat pump provided. Reference: Section C503.3, IECC 2024:

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.