Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0726-01160
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/23/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions regarding this review, please contact CDRC@TucsonAZ.Gov
Unit number missing from site plan. Please add unit number to site plan and resubmit:
Step-by-Step instructions on how to resubmit plans: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
07/27/2026 Commercial Mechanical Express REQUIRES RESUBMIT Replacement of AC units for the residential occupancies will require a heating/cooling load calculation to justify the capacities of the units being installed. The efficiency rating of the replacement units will have to be equal to or exceed the minimum required by federal law for this geographic location. All single-phase equipment not operational on January 1, 2023, in the Southwest region, must have an EnergyGuide label identifying a SEER2 or SEER2/EER2 rating. Reference: Sections R403.7 and R501.4, IECC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
07/23/2026 PDSD Application Completeness Express REVIEW COMPLETED