Permit Number: TC-COM-0726-01157
Parcel: 13734001D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0726-01157
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2026 Site Engineering NOT REQUIRED
08/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/07/2026 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01157
ADDRESS/PARCEL: (1694 W VALENCIA RD TUCSON, AZ 85746)
TC-COM-0526-00787 (3002 E GRANT RD Unit:UNIT 2 TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. SEAL/SIGNATURE/DATE SIGNED
a. The Architectural sheets have the note, “Preliminary – Not for Construction or Recording”. Please remove this note. The seal/signature/date signed are missing, please have the architect address this issue.
b. The Mechanical sheets have the note, “Preliminary – Not for Construction or Recording”. Please remove this note. The seal/signature/date signed are missing, please have the Mechanical Engineer address this issue.
c. The Electrical sheets have the note, “Preliminary – Not for Construction or Recording”. Please remove this note. The seal/signature/date signed are missing, please have the Electrical Engineer address this issue.
d. The Plumbing sheets have the note, “Preliminary – Not for Construction or Recording”. Please remove this note. The seal/signature/date signed are missing, please have the Plumbing Engineer address this issue.
2. CASH WRAP COUNTER
a. Please provide a drawing illustrating the following.
b. The tops of work surfaces shall be 28 inches min & 34 inches max above the floor per ICC A117.1 sec 902.4.
c. Sec 306.3.3 Knee clearance shall be 11 inches min in depth at 9 inches above the floor, and 8 inches min in depth at 27 inches above the floor.
d. Sec 306.2.4 Additional toe clearance space extending greater than 6 inches beyond the available knee clearance at 9 inches above the floor.
e. Sec 306.3 Knee clearance shall be 30 inches min in width.
f. 904.3.2 Parallel approach, the counter surface 36 inches min length.
g. 904.3.3 Forward approach, the counter surface 30 inches min length.
3. FIRE PARTITION
a. Tenant separation using fire partition with fire-resistance rating of not less than 1 hour per IBC 402.4.2.1 and IBC 708 extend from the top of the foundation or floor/ceiling assembly below to the underside of the floor or roof sheathing, deck or slab above shall have penetration complying to IBC 714 and joints complying with IBC 715 protected by an approved fire-resistant joint system to resist the passage of fire for a time period not less than the required fire-resistance rating of the wall, floor or roof in or between which the system is installed.
b. Please provide a drawing illustrating this wall assembly.
4. DRINKING FOUNTAIN
a. Water Plumbing Plan sheet P6 does not show drinking fountain to be connected to water and waste line.
b. This is not a restaurant providing drinking water in a container free of charge (vending machine selling water is shown), therefore drinking fountains shall be required. In other occupancies where three or more drinking fountains are required, water dispensers shall be permitted to be substituted for not more than 50 percent of the required number of drinking fountains. IPC 410.4
5. TURNING SPACE
a. The turning space shall be a circular space with a 67-inch minimum diameter. ICC A117.1 sec 304.3.1.1
b. The back area at the Dryers requires this accessible turning space.
c. Please resolve this code required item on your drawings.
6. DEAD END CORRIDOR
a. The space behind the dryers is a dead end corridor.
b. Please address this issue properly to be code compliant, show the length dimension on the plan.
c. Where more than one exit or exit access doorway is required, the exit access shall be arranged such that dead-end corridors do not exceed 20 feet in length. IBC 1020.5
7. Please resubmit.
08/04/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01157 (1694 W VALENCIA RD TUCSON, AZ 85746)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide GFCI protection per NEC 210.8(B)(14). Double. Readily accessible per NEC 210.8.
3. Provide GFCI protection per NEC 210.8(D)(11). Readily accessible per NEC 210.8.
4. Provide the new Service Lateral conductor size and type.
08/10/2026 Commercial Mechanical REQUIRES RESUBMIT 1. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. remove the “Preliminary, not for Construction” label from the drawings.). Reference: Section 107.2.1, IBC 2024.
2. Coordinate the keynotes on M5 with the mechanical rooftop plan. Reference: Section 107.2.1, IBC 2024.
3. Provide a sequence of operation for the restroom exhaust fans (i.e., explain the “delay timer switch” operation).
4. Provide a detail of the dryer exhaust duct systems. Reference: Section 107.2.1, IBC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
08/10/2026 Commercial Plumbing REQUIRES RESUBMIT 1. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. remove the “Preliminary, not for Construction” label from the drawings.). Reference: Section 107.2.1, IBC 2024.
2. .Revise the location of the cold water shut off valve in the water heater detail, 1/P10, so that expansion tank is located downstream of the check valve and the shut off valve. Reference: Section 607.3, IPC 2024.
3. Provide cleanouts for all horizontal drains; the cleanouts shall not be located greater than 100-feet apart, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2024.
4. An approved 2-way cleanout fitting is a single fitting, not a field-assembled group of individual fittings as shown in detail 3/P10. Reference: Section 708.1.9, IPC 2024.
5. Show that each trench drain has been vented in accordance with one of the methods shown in the IPC. Reference: Sections 901.2.1 and 905.2, IPC 2024.
6. Revise the configuration of the natural gas sediment traps, as shown on P8, to comply with the requirements of Section 408.4, IFGC 2024 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible).
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
08/10/2026 Fire New Construction REQUIRES RESUBMIT -Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
08/11/2026 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Jeffrey W. Cassidy, Planner
Planning & Development Services Department – Current Zoning Review Section

PROJECT:
TC-COM-0726-01157 – Commercial – Laundromat Tenant Improvement in existing retail space
1694 W VALENCIA RD TUCSON, AZ 85746 (C-2 Zoning)
Commercial Building Plan Review – 1st Review

TRANSMITTAL DATE:
August 11, 2026

1. COMMENT: On sheet 0, under Project Information, update the Use from Business to Commercial Services-Personal Services per UDC 4.9.13.P.

2. COMMENT: The vehicular parking requirements for Personal Services are 1 stall per 300 square feet of gross floor area. Update this from the 200 currently shown under Project Information on sheet 0.

3. COMMENT: Per Comment #2, ten vehicular spaces will be required. There are two places on sheet 0 where this will need to be updated per UDC TABLE 7.4.4-1.

4. COMMENT: Two short-term and two long-term bicycle parking spaces will need to be provided per UDC Table 7.4.8-1. Provide the locations and appropriate details in the drawing package.

5. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

6. COMMENT: Corrected commercial building permit.

7. COMMENT: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home .

Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf

If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code .
08/10/2026 Water - PDSD REQUIRES RESUBMIT Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. remove the “Preliminary, not for Construction” label from the drawings.). Reference: Section 107.2.1, IBC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
07/28/2026 PDSD Application Completeness Express REVIEW COMPLETED