Permit Number: TC-COM-0726-01157
Parcel: 13734001D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0726-01157
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2026 Commercial Building APPROVED
10/12/2026 Site Zoning APPROVED
10/12/2026 Water - PDSD APPROVED
10/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/01/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01157 (1694 W VALENCIA RD TUCSON, AZ 85746)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

>>> comments were not addressed.

1. Provide GFCI protection per NEC 210.8(B)(14). Double. Readily accessible per NEC 210.8. >>> All receptacles withing the laundry area require GFCI protection, including all washing machines, wall receptacles and drier receptacles.
2. Provide GFCI protection per NEC 210.8(D)(11). Readily accessible per NEC 210.8. >>> All dryer Outlets are required to have GFCI protection.
10/12/2026 Commercial Mechanical REQUIRES RESUBMIT 1. Revise the operation of the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Footnote g, Table 403.3.1.1, IMC 2024. [initial comment: Provide a sequence of operation for the restroom exhaust fans (i.e., explain the “delay timer switch” operation).]
2. The dryer exhaust detail applies to only two of the three banks of dryers. Show how the arrangement of the exhaust ducts for the center bank of dryers comply with the manufacturer’s installation instructions. [Initial comment: Provide a detail of the dryer exhaust duct systems. Reference: Section 107.2.1, IBC 2024.]
3. The dryer manufacturer’s installation instructions specify a minimum fresh air inlet area 1.3 square feet per DE-650 dryer and 1.75 square feet per DE-683 dryer (free area, not including resistance from grilles or louvers). Verify that the proposed gravity ventilators provide the required free area. Reference: Section 304.1, IMC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
10/12/2026 Commercial Plumbing REQUIRES RESUBMIT 1. 1. Vents shall be installed to drain back to the drainage pipe by gravity. The design shown creates a trap for water to collect and restrict airflow. Reference: Section 905.2, IPC 2024. [Initial comment: Show that each trench drain has been vented in accordance with one of the methods shown in the IPC. Reference: Sections 901.2.1 and 905.2, IPC 2024.]
2. Comment not addressed; the drawing is unchanged. [Initial comment: Revise the configuration of the natural gas sediment traps, as shown on P8, to comply with the requirements of Section 408.4, IFGC 2024 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible).]
3. Revise the water heater detail, 1/P10, to show the hot water recirculation shown on P6. Reference: Section 107.2.1, IBC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
10/09/2026 Fire New Construction REVIEW COMPLETED
09/29/2026 PDSD Application Completeness Express REVIEW COMPLETED