Permit Number: TC-COM-0726-01146
Parcel: 13333026B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0726-01146
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2026 Fire New Construction Standard NOT REQUIRED
08/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/10/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01146
ADDRESS/PARCEL: (1051 N HARRISON RD TUCSON, AZ 85748)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. DISTANCE TO PROPERTY LINE
a. The distance to the property line to the closest portion of the proposed structure is approximately 1 foot.
b. This means that the structure is built within the setback requirement.
c. This also means that the Fire Separation Distance is not met per International Building Code section 705.5 and Table 705.5
d. Please coordinate with our Zoning Department in order to remedy this condition.
e. Please have your design professional address this issue.
2. EAST STRUCTURAL LEG
a. This leg seems to land on an existing parking stall.
b. This means that the parking count has been reduced. Please confirm whether this parking stall count make this facility not compliant on the parking count. Please coordinate wit Zoning Department.
c. Please show the parking stall paint stripe on the plan.
3. Please provide the distance between this proposed canopy and the existing structure.
a. The fire separation distance seems not compliant.
4. Please resubmit
08/05/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01146 (1051 N HARRISON RD TUCSON, AZ 85748)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Where subject to physical damage, conductors, raceways, equipment, and cables shall be protected. Provide protection against damage as necessary for the Structural Leg mounted inverters and combiner panel. NEC 300.4 Protection Against Physical Damage, NEC110.27(B) Prevent Physical Damage. Show equipment is protected from physical damage or provide tire stops or bollards or other means to protect from car impacts.
2. Provide a Grounding Electrode System at the detached structure per 250.31(A). Grounding electrode system and grounding electrode conductor. Required.
3. Provide appropriate grounding and bonding of all metal structures, per all relevant sections of NEC 250 (example sections 250.4(A), 250.20, 250,32, 250.104).
4. Provide for local disconnecting means at the structure for the canopy lighting as required per NEC art 225.31-32.

250.31(A) Grounding electrode system and grounding electrode conductor. Required.
250.31(B) equipment grounding conductor, grounding bonding equipment and structural metal. Sized accordance with 250.122.

250.32(D), disconnecting means located in separate building or structure. See also 225.31(B) exception No. 1.
08/05/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0726-01146 (1051 N HARRISON RD TUCSON, AZ 85748)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
a. Clarify if any existing lighting fixtures are being move, removed or if there are new under canopy fixtures being added.
2. Show any new under canopy lighting fixtures as full-cutoff, OLC 401.2.1(3).
3. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
07/24/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-0726-01146 (1st Review)
Project: Roof mounted solar install on top of a structure ; 45 modules DC SIZE: 26.325 KW ; AC SIZE: 22.8 KW line side tap.
Location: 1051 N HARRISON RD
Review Date: 7/24/2026
Reviewer: Marco Contreras – Engineering Associate - Site Engineering
Reviewer Contact: Marco.contreras@tucsonaz.gov
Related cases:

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering.
To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files.
Site Engineering Review Comments:
1. The proposed solar parking canopy, and all other exterior modifications proposed at this commercial site will require the submission of a Development Package (Site plan) in accordance with UDC §7.4.3.E. Per UDC §3.3.3.G.2.c, A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. Please coordinate through email to confirm any additional studies required based on site conditions & reviewer comments. Note that the Development Package is a separate permit submittal, and must be processed independently of the building plans.
2. Site Engineering is unable to fully review and approve permit TC-COM-0726-01146 until the associated Development Package is reviewed and approved by all reviewers.
08/05/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0726-01146
1051 N. Harrison Rd. Tucson, AZ 85748
Roof Mounted Solar on Top of New Carport Structure (1st Review)

TRANSMITTAL DATE: 8/5/2026

This site is located in the R-2 (UDC 4.7.9) and C-1 (UDC 4.7.20) zones. Animal Service is an allowed use subject to Use Specific Standards 4.9.4.D.1, .2, .3, & .4 and 4.9.13.O or 4.9.4.D.7 & 4.9.4.D.10-.15 (UDC Table 4.8-4).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the minimum requirements is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/submittal_requirements.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
07/22/2026 PDSD Application Completeness Express REVIEW COMPLETED