Permit Number: TC-COM-0726-01143
Parcel: 10610002A

Address:
3749 N ROMERO RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0726-01143
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2026 Commercial Building Standard APPROVED Submitted SIC dated 9/2/26 is incomplete: see list of special inspections within the list of conditions, please correct it and resubmit.
09/22/2026 Commercial Electrical Standard APPROVED
09/29/2026 Commercial Mechanical Standard APPROVED
09/29/2026 Commercial Plumbing Standard APPROVED
09/14/2026 Site Engineering Standard APPROVED
09/28/2026 Site Zoning Standard APPROVED
10/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/24/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0726-01143 (3749 N ROMERO RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. A development package, reviewed under the UDC, does not apply to the building code and outdoor lighting requirements. Per OLC 104.2.1(3), the lumen calculations are to be applied to the permitted parcel.
2. An appeal to the building official is required to justify using multiple parcels in the calculations. The appeal will need to include details on how the lumen totals across multiple parcels will be tracked and maintained, such that one parcel does not utilize all the lumens allowed for the other parcel.
3. Otherwise, compliance with previous review comments is required.
09/10/2026 Addressing Validation REVIEW COMPLETED
09/09/2026 PDSD Application Completeness Express REVIEW COMPLETED