Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0726-01137
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2026 | Commercial Electrical Express | NOT REQUIRED | like-for-like replacement. | ||
| 07/21/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/21/2026 | Commercial Mechanical Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0726-01137 ADDRESS/PARCEL: 6300 S HEADLEY RD Unit:BLDG 5 UNIT 5101 TUCSON, AZ 85746 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Replacement of commercial AC units constitutes new work. Therefore, the submittal will require a heating/cooling load calculation for the building to justify the capacity of the unit being installed (Sections C403.3.1 and C403.2.2, IECC 2024). The replacement unit shall also comply with Sections C403.3.2 and C403.4, IECC 2024, for equipment performance and controls. |
||
| 07/20/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |