Permit Number: TC-COM-0726-01136
Parcel: 14025101A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0726-01136
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/20/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01136 (6001 S PARK AV Unit:UNIT 21 TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. The replacement of the existing service equipment requires the submission of a basic riser-diagram.
2. Provide an electrical riser diagram, NEC 230.9.
a. Show each meter and address/unit associated with each meter.
b. Show bus bar rating and AIC ratings of the new equipment.
c. Highlight the parts, conductors, equipment, etc, being replaced. Provide sizing and other info as needed to verify code compliance.
3. Provide an updated panel schedule showing the circuits and description of each circuit.
07/20/2026 PDSD Application Completeness Express REVIEW COMPLETED